ASTM-D3382 2007
$40.63
D3382-07 Standard Test Methods for Measurement of Energy and Integrated Charge Transfer Due to Partial Discharges (Corona) Using Bridge Techniques
Published By | Publication Date | Number of Pages |
ASTM | 2007 | 8 |
1.1 These test methods cover two bridge techniques for measuring the energy and integrated charge of pulse and pseudoglow partial discharges:
1.2 Test Method A makes use of capacitance and loss characteristics such as measured by the transformer ratio-arm bridge or the high-voltage Schering bridge (Test Methods D 150). Test Method A can be used to obtain the integrated charge transfer and energy loss due to partial discharges in a dielectric from the measured increase in capacitance and tan with voltage. (See also IEEE 286 and IEEE 1434)
1.3 Test Method B makes use of a somewhat different bridge circuit, identified as a charge-voltage-trace (parallelogram) technique, which indicates directly on an oscilloscope the integrated charge transfer and the magnitude of the energy loss due to partial discharges.
1.4 Both test methods are intended to supplement the measurement and detection of pulse-type partial discharges as covered by Test Method D 1868, by measuring the sum of both pulse and pseudoglow discharges per cycle in terms of their charge and energy.
This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. Specific precaution statements are given in Section 7.
PDF Catalog
PDF Pages | PDF Title |
---|---|
1 | Scope Referenced Documents Terminology |
2 | Summary of Test Methods Significance and Use Sources of Errors |
3 | Hazards Procedure Precision and Bias Interferences FIG. 1 |
4 | Procedure Calibration of Oscilloscope Coefficients FIG. 2 FIG. 3 |
5 | Calculation Report Precision and Bias Keywords A1. LIST OF SYMBOLS |
6 | A2. CIRCUIT COMPONENTS AND MEASUREMENT PROCEDURE FOR TEST METHOD B (SEE A2.1 Apparatus A2.2 High-Voltage Divider A2.3 Oscilloscope A2.4 High-Voltage Transformer A2.5 Measurement Procedure |
7 | A3. ADDITIONAL MEASUREMENT ANALYSIS (TEST METHOD B) A3.1 A3.2 A3.3 REFERENCES |