BS EN 60730-1:2016
$215.11
Automatic electrical controls – General requirements
Published By | Publication Date | Number of Pages |
BSI | 2016 | 292 |
In general, this part of IEC 60730 applies to automatic electrical controls for use in, on, or in association with equipment for household and similar use. The equipment may use electricity, gas, oil, solid fuel, solar thermal energy, etc., or a combination thereof.
NOTE 1 Throughout this standard the word “equipment” means “appliance and equipment.”
EXAMPLE 1 Controls for appliances within the scope of IEC 60335.
This International Standard is applicable to controls for building automation within the scope of ISO 16484.
This standard also applies to automatic electrical controls for equipment that may be used by the public, such as equipment intended to be used in shops, offices, hospitals, farms and commercial and industrial applications.
EXAMPLE 2 Controls for commercial catering, heating and air-conditioning equipment.
This standard is also applicable to individual controls utilized as part of a control system or controls which are mechanically integral with multifunctional controls having non-electrical outputs.
EXAMPLE 3 Independently mounted water valves, controls in smart grid systems and controls for building automation systems within the scope of ISO 16484-2.
This standard is also applicable to relays when used as controls for IEC 60335 appliances. Additional requirements for the safety and operating values of relays when used as controls for IEC 60335 appliances are contained in Annex U.
NOTE 2 These requirements are referred to in the scope of IEC 61810-1.
NOTE 3 This standard is intended to be used for the testing of any stand-alone relay which is intended to be used as a control of an appliance according to IEC 60335-1. It is not intended to be used for any other stand-alone relay, or to replace the IEC 61810 series of standards.
This standard does not apply to automatic electrical controls intended exclusively for industrial process applications unless explicitly mentioned in the relevant part 2 or the equipment standard.
This standard applies to controls powered by primary or secondary batteries, requirements for which are contained within the standard, including Annex V.
1.1.1 This International Standard applies to the inherent safety, to the operating values, operating times, and operating sequences where such are associated with equipment safety, and to the testing of automatic electrical control devices used in, or in association with, equipment.
This standard applies to controls using thermistors, see also Annex J.
This standard is also applicable to the functional safety of low complexity safety related systems and controls.
1.1.2 This standard applies to automatic electrical controls, mechanically or electrically operated, responsive to or controlling such characteristics as temperature, pressure, passage of time, humidity, light, electrostatic effects, flow, or liquid level, current, voltage, acceleration, or combinations thereof.
1.1.3 This standard applies to starting relays, which are a specific type of automatic electrical control, intended to switch the starting winding of a motor. Such controls may be built into, or be separate from, the motor.
NOTE Starting relays are tested as voltage sensing or current sensing controls.
1.1.4 This standard applies to manual controls when such are electrically and/or mechanically integral with automatic controls.
NOTE Requirements for manual switches not forming part of an automatic control are contained in IEC 61058-1.
1.1.5 This standard applies to a.c. or d.c. powered controls with a rated voltage not exceeding 690 V a.c. or 600 V d.c.
1.1.6 This standard does not take into account the response value of an automatic action of a control, if such a response value is dependent upon the method of mounting the control in the equipment. Where a response value is of significant purpose for the protection of the user, or surroundings, the value defined in the appropriate household equipment standard or as determined by the manufacturer shall apply.
1.1.7 This standard applies also to controls incorporating electronic devices, requirements for which are contained in Annex H.
1.1.8 This standard applies also to controls using NTC or PTC thermistors, requirements for which are contained in Annex J.
1.1.9 This standard applies to the electrical and functional safety of controls capable of receiving and responding to communications signals, including signals for power billing rate and demand response.
The signals may be transmitted to or received from external units being part of the control (wired), or to and from external units which are not part of the control (wireless) under test.
1.1.10 This standard does not address the integrity of the output signal to the network devices, such as interoperability with other devices unless it has been evaluated as part of the control system.
PDF Catalog
PDF Pages | PDF Title |
---|---|
5 | Contents |
6 | Annex ZA (normative) Normative references to international publications with their corresponding European publications |
11 | Annex ZB (normative) Special national conditions |
13 | Annex ZC (informative) A-deviations |
14 | Annex ZD (normative) EMC immunity for controls ZD.1 Electromagnetic compatibility (EMC) requirements – Immunity |
15 | ZD.2 Classification of the control ZD.3 Information |
16 | ZD.4 Evaluation of compliance |
17 | ZD.5 Surge immunity test |
18 | ZD.6 Electrical fast transient/burst immunity test |
19 | ZD.7 Radio-frequency electromagnetic field immunity ZD.7.1 Immunity to conducted disturbances ZD.7.2 Electrostatic discharge |
20 | ZD.8 Immunity to radiated electromagnetic fields ZD.9 Immunity to power-frequency magnetic fields |
21 | ZD.10 Test of the influence of voltage dips and voltage interruption in the power supply network |
22 | English CONTENTS |
27 | FOREWORD |
30 | 1 Scope and normative references |
36 | 2 Terms and definitions |
58 | 3 General requirements 4 General notes on tests |
62 | 5 Rating 6 Classification |
70 | 7 Information |
73 | Tables Table 1 (7.2 of edition 3) – Required information and methods of providing information (1 of 4) |
79 | 8 Protection against electric shock |
82 | 9 Provision for protective earthing |
84 | Table 2 (9.3.2 of edition 3) – Quick connect terminal dimensions (Canada and USA) |
85 | 10 Terminals and terminations |
86 | Table 3 (10.1.4 of edition 3) – Minimum cross-sectional area of conductors |
88 | Table 4 (10.1.8 of edition 3) – Terminal conductors |
89 | Table 5 (10.1.9 of edition 3) – Conductor pull test values |
91 | Table 6 (10.2.1 of edition 3) – Nominal cross-sectional areas of conductors |
92 | Table 7 (10.2.4.2 of edition 3) – Material and plating for tabs Table 8 (10.2.4.3 of edition 3) – Axial force values for tab insertion and withdrawal |
93 | 11 Constructional requirements |
103 | Table 9 (11.7.2 of edition 3) – Pull and torque values |
104 | Table 10 (11.8.2 of edition 3) – Minimum cord conductor sizes |
111 | 12 Moisture and dust resistance |
113 | 13 Electric strength and insulation resistance |
117 | Table 13 (14.1 of edition 3) – Maximum heating temperatures (1 of 3) |
121 | 15 Manufacturing deviation and drift |
122 | 16 Environmental stress |
123 | 17 Endurance |
125 | Table 14 (17.2.1 of edition 3) – Electrical conditions for the overvoltage test (this table applies in all countries except Canada, and the USA) |
130 | 18 Mechanical strength |
134 | Table 19 (18.7 of edition 3) – Pull-cord force test values |
135 | 19 Threaded parts and connections |
136 | Table 20 (19.1 of edition 3) – Threaded parts torque test values |
138 | 20 Creepage distances, clearances and distances through solid insulation |
139 | Table 21 (20.1 of edition 3) – Rated impulse voltage for equipment energized directly from the supply mains (from IEC 60664-1:2007, Table F.1) |
140 | Table 22 (20.2 of edition 3) – Clearances for insulation co-ordination(from IEC 606641:2007, Table F.2) |
144 | Table 23 (20.3 of edition 3) – Minimum creepage distances for basic insulation |
145 | Table 24 (20.4 of edition 3) – Minimum creepage distancesfor functional insulation |
147 | 21 Resistance to heat, fire and tracking |
149 | 22 Resistance to corrosion Table 25 (21.4 of edition 3) – Mercury switch shortcircuit conditions |
150 | 23 Electromagnetic compatibility (EMC) requirements – Emission |
151 | 24 Components |
153 | 25 Normal operation 26 Electromagnetic compatibility (EMC) requirements – Immunity 27 Abnormal operation |
154 | Table 26 (27.2.3 of edition 3) – Maximum winding temperature (for test of mechanical blocked output conditions) |
156 | 28 Guidance on the use of electronic disconnection Figures Figure 1 – Test pin |
157 | Figure 2 – Standard test finger |
158 | Figure 3 – Test nail |
159 | Figure 4 – Impact test for free-standing controls Figure 5 – Tumbling barrel |
160 | Figure 6 – Ball-pressure apparatus Figure 7 – Void Figure 8 – Apparatus for testing durability of markings on rating labels |
161 | Figure 9 – Apparatus for flexing test |
162 | Figure 10 – Screw terminals and stud terminals (1 of 2) |
164 | Figure 11 – Pillar terminals |
165 | Figure 12 – Mantle terminals |
166 | Figure 13 – Saddle and lug terminals |
167 | Figure 14 – Tabs |
168 | Figure 15 – Tabs for non-reversible connectors |
169 | Figure 16 – Receptacles |
170 | Figure 17 – Measurement of creepage distance and clearance |
171 | Annexes Annex A (normative) Indelibility of markings |
173 | Annex B (normative) Measurement of creepage distances and clearances in air Table B.1 – Value of X |
174 | Figure B.1 – Narrow groove Figure B.2 – Wide groove Figure B.3 – V-shaped groove |
175 | Figure B.4 – Rib Figure B.5 – Uncemented joint with narrow groove Figure B.6 – Uncemented joint with wide groove |
176 | Figure B.7 – Uncemented joint with narrow and wide grooves Figure B.8 – Diverging side walls |
177 | Figure B.9 – Narrow recess Figure B.10 – Wide recess Figure B.11 – Conductive floating part |
178 | Annex C (normative) Cotton used for mercury switch test (not applicable in the countries members of CENELEC) |
179 | Annex D (informative) Heat, fire and tracking |
180 | Annex E (normative) Circuit for measuring leakage current Figure E.1 – Circuit for measuring leakage currents |
181 | Annex F (informative) Fire hazard testing |
182 | Annex G (normative) Heat and fire resistance tests |
184 | Annex H (normative) Requirements for electronic controls |
203 | Table H.1 (H.11.12.7 of edition 3) – Acceptable measures to address fault/errors a (1 of 6) |
210 | Figure H.1 – V-Model for the software life cycle Table H.2 – Semi-formal methods |
211 | Table H.3 – Software architecture specification |
212 | Table H.4 – Module design specification Table H.5 – Design and coding standards |
213 | Table H.6 – Software module testing |
214 | Table H.7 – Software integration testing Table H.8 – Software safety validation |
215 | Table H.9 (H.11.12.6 of edition 3) – Combinations of analytical measures during hardware development |
216 | Table H.10 – Data exchange |
217 | Table H.11 – Examples of defences against unauthorised accessand transmission failure modes |
222 | Table H.12 (H.23 of edition 3) – Emission |
223 | Table H.13 (H.26.2.1 of edition 3) – Applicable test levels |
225 | Table H.14 – Voltage dips, short interruptions and voltage variations |
226 | Figure H.2 – Voltage variation test Table H.15 (H.26.5.4.2 of edition 3) – Test values for voltage variations |
228 | Table H.16 (H.26.8.2 of edition 3) – Test voltages for test level 2 (depending on the installation class conditions) |
229 | Table H.17 – Test level for electrical fast transient burst test |
230 | Figure H.3 – Ring wave characteristics (open-circuit voltage) Figure H.4 – Schematic of a ring wave generator 0,5 (s /100 kHz |
231 | Table H.19 (H.26.12.2.1 of edition 3) – Test levels for conducted disturbances on mains and I/O lines |
232 | Table H.20 (H.26.12.3.1 of edition 3) – Test level for immunity to radiated electromagnetic fields Table H.21 – Increased test level for radiated immunity(ISM, GSM, DECT bands) |
233 | Table H.22 (H.26.13.2 of edition 3) – Test level for supply frequency variations |
234 | Table H.23 (H.26.14.2 of edition 3) – Test level for continuous fields |
235 | Figure H.5 – Example of an electronic circuit with low power points |
237 | Table H.24 (H.27.1 of edition 3) – Electrical/electronic component fault modes table (1 of 3) |
246 | Annex J (normative) Requirements for thermistor elements and controls using thermistors |
248 | Table J.1 – Maximum current |
249 | Table J.2 (J.7, 7.2 of edition 3) – Normal operating conditions |
250 | Table J.3 – Samples for the test (clause reference) |
251 | Table J.4 – Electrical and thermal ratings of a thermistor |
253 | Table J.5 – Additional items to Table 1 |
255 | Table J.6 – Sequence of calibration and conditioning tests for PTC thermistors |
256 | Table J.7 – Classes for PTC sensing thermistors |
257 | Table J.8 – Sequence of calibration and conditioning tests for NTC thermistors Table J.9 – Classes for NTC sensing thermistors |
260 | Table J.10 – Number of cycles for endurance test |
261 | Table J.11 – Ageing test temperature |
262 | Figure J.1 – Test circuit for inrush-current limiting thermistor endurance test Table J.12 – Number of cycles for endurance test |
264 | Annex K (informative) Nominal voltages of supply systems for different modes of overvoltage control Table K.1 – Inherent control or equivalent protective control |
265 | Table K.2 – Cases where protective control is necessary and control is provided by surge arresters having a ratio of clamping voltage to rated voltagenot smaller than that specified by IEC 60099-1 |
266 | Annex L (normative) Overvoltage categories |
267 | Annex M (informative) Typical usage Table M.1 – Typical usage |
268 | Annex N (normative) Pollution degrees |
269 | Annex P (normative) Printed circuit board coating performance test Table P.1 – Environmental cycling conditions |
270 | Figure P.1 – Test sample |
271 | Annex Q (normative) Printed circuit board coating performance test Table Q.1 – IEC 60664-3 test levels or conditions |
272 | Figure Q.1 – Test sample |
273 | Figure Q.2 – Examples of land configurations (see also Figure Q.1) |
274 | Annex R (informative) Explanatory notes for surge immunity test |
277 | Figure R.1 – Example of surge protection by shielding in buildings with common earth reference systems Figure R.2 – Example of secondary surge protection in buildings with separate common earth reference systems |
278 | Figure R.3 – Example of primary and secondary surge protection of indoor/outdoor equipment |
279 | Annex S (informative) Guidance for applying Clause 20 Figure S.1 – Guidance flowchart for application of requirements of Clause 20 |
280 | Table S.1 – Example A – Using Annex S guidance for applying Clause 20 Table S.2 – Example B – Using Annex S guidance for applying Clause 20 |
281 | Annex T (normative) Requirements for SELV and PELV |
284 | Annex U (normative) Requirements for relays when used as controls in IEC 60335 appliances |
287 | Annex V (normative) Requirements for controls powered by secondary batteries (rechargeable) |
289 | Bibliography |