BS EN IEC 61400-21-1:2019+A11:2020
$215.11
Wind energy generation systems – Measurement and assessment of electrical characteristics. Wind turbines
Published By | Publication Date | Number of Pages |
BSI | 2020 | 150 |
This part of IEC 61400 includes:
-
definition and specification of the quantities to be determined for characterizing the electrical characteristics of a grid-connected wind turbine;
-
measurement procedures for quantifying the electrical characteristics;
-
procedures for assessing compliance with electrical connection requirements, including estimation of the power quality expected from the wind turbine type when deployed at a specific site.
The measurement procedures are valid for single wind turbines with a three-phase grid connection. The measurement procedures are valid for any size of wind turbine, though this part of IEC 61400 only requires wind turbine types intended for connection to an electricity supply network to be tested and characterized as specified in this part of IEC 61400.
The measured characteristics are valid for the specific configuration and operational mode of the assessed wind turbine product platform. If a measured property is based on control parameters and the behavior of the wind turbine can be changed for this property, it is stated in the test report. Example: Grid protection, where the disconnect level is based on a parameter and the test only verifies the proper functioning of the protection, not the specific level.
The measurement procedures are designed to be as non-site-specific as possible, so that electrical characteristics measured at for example a test site can be considered representative for other sites.
This document is for the testing of wind turbines; all procedures, measurements and tests related to wind power plants are covered by IEC 61400-21-2.
The procedures for assessing electrical characteristics are valid for wind turbines with the connection to the PCC in power systems with stable grid frequency.
NOTE
For the purposes of this document, the following terms for system voltage apply:
-
Low voltage (LV) refers to Un ≤ 1 kV;
-
Medium voltage (MV) refers to 1 kV < Un ≤ 35 kV;
-
High voltage (HV) refers to 35 kV < Un ≤ 220 kV;
-
Extra high voltage (EHV) refers to Un > 220 kV.
PDF Catalog
PDF Pages | PDF Title |
---|---|
2 | undefined |
4 | European foreword |
5 | 1 Modification to the title page 2 Modification to the European foreword |
7 | English CONTENTS |
15 | FOREWORD |
17 | INTRODUCTION |
18 | 1 Scope 2 Normative references |
19 | 3 Terms and definitions |
27 | Figures Figure 1 – Example of step response |
30 | 4 Symbols and units |
31 | 5 Abbreviated terms |
32 | 6 Wind turbine specification 7 Test conditions and test systems 7.1 General 7.2 Overview of required test levels |
33 | 7.3 Test validity Tables Table 1 – Overview of required test levels |
34 | 7.4 Test conditions |
35 | 7.5 Test equipment |
36 | Figure 2 – Measurement system description including the most significant components Table 2 – Specification of requirements for measurement equipment |
37 | 8 Measurement and test of electrical characteristics 8.1 General 8.2 Power quality aspects 8.2.1 General 8.2.2 Flicker during continuous operation |
38 | Figure 3 – Fictitious grid for simulation of fictitious voltage |
40 | 8.2.3 Flicker and voltage change during switching operations |
43 | 8.2.4 Harmonics, interharmonics and higher frequency components |
45 | 8.3 Steady-state operation 8.3.1 General 8.3.2 Observation of active power against wind speed |
46 | Figure 4 – Active power as a function of the wind speed (example) Table 3 – Number of 10-min time-series per wind speed bin Table 4 – Number of measurements per power bin (10 min average) |
47 | 8.3.3 Maximum power Figure 5 – Number of measurements in power bins (example) Figure 6 – Number of measurements in wind speed bins (example) |
48 | Table 5 – Measured maximum active power values |
49 | 8.3.4 Reactive power characteristic (Q = 0) 8.3.5 Reactive power capability |
50 | 8.3.6 Voltage dependency of PQ diagram Figure 7 – Example of PQ capability diagram for a given voltage at WT level |
51 | 8.3.7 Unbalance factor |
52 | 8.4 Control performance 8.4.1 General 8.4.2 Active power control |
53 | Figure 8 – Adjustment of active power reference value Figure 9 – Example of active power response step |
54 | Table 6 – Accuracy of the active power control values Table 7 – Results from the active power reference test |
55 | 8.4.3 Active power ramp rate limitation |
56 | Figure 10 – Example of available active power and activepower in ramp rate limitation modefigue Table 8 – Active power ramp rate calculation |
57 | 8.4.4 Frequency control Figure 11 – Example of an active power control function P=f(f), with the different measurement points and related steps of frequency |
58 | Table 9 – Example of Settings for the frequency dependent active power function |
59 | 8.4.5 Synthetic inertia |
60 | 8.4.6 Reactive power control Figure 12 – Synthetic inertia – definitions |
61 | Figure 13 – Test for static error |
62 | Figure 14 – Test of dynamic response (example) |
63 | 8.5 Dynamic performance 8.5.1 General 8.5.2 Fault ride-through capability Table 10 – Test for static error Table 11 – Test for dynamic response |
64 | Figure 15 – Example UVRT test equipment |
65 | Figure 16 – Tolerances of the positive sequence voltage for the undervoltage eventwith disconnected WT under test |
66 | Figure 17 – Tolerance of positive sequence overvoltage event |
67 | Figure 18 – Example OVRT capacitor test unit |
68 | Figure 19 – Example of an undervoltage test chart Table 12 – Example of undervoltage events |
69 | Figure 20 – Example of an overvoltage capability curve |
70 | Table 13 – Example of overvoltage tests |
71 | 8.6 Disconnection from grid 8.6.1 General 8.6.2 Grid protection |
72 | Table 14 – Grid protection tests |
73 | Figure 21 – Example of step ramp for overvoltage or frequency testing |
74 | Figure 22 – Example of pulse ramp for over voltage or frequency testing Figure 23 – Example of the test levels to determine the release time |
75 | 8.6.3 Test of rate of change of frequency RoCoF (df/dt) protection device |
76 | 8.6.4 Reconnection test |
77 | Annex A (informative)Reporting A.1 Overview A.2 General Table A.1 – General report information |
78 | Table A.2 – General data Table A.3 – Nominal data Table A.4 – Test conditions |
79 | A.3 Power quality aspects Figure A.1 – Voltage flicker Pst vs. active power Figure A.2 – Flicker coefficient c(30°) vs. active power Table A.5 – Flicker coefficient per power bin (95th percentile) |
80 | Figure A.3 – Flicker coefficient c(50°) vs. active power Figure A.4 – Flicker coefficient c(70°) vs. active power Figure A.5 – Flicker coefficient c(85°) vs. active power Table A.6 – Start-up at cut in wind speed |
81 | Figure A.6 – Time series of 3-phase voltages as RMSof start-up at the wind speed of … m/s Figure A.7 – Time series of 3-phase currents as RMSof start-up at the wind speed of … m/s Figure A.8 – Time series of active and reactive powerof start-up at the wind speed of … m/s Table A.7 – Start-up at nominal active power |
82 | Figure A.9 – Time series of 3-phase voltages as RMSof start-up at nominal active power Figure A.10 – Time series of 3-phase currents as RMSof start-up at nominal active power Figure A.11 – Time series of active and reactive powerof start-up at nominal active power Table A.8 – Worst-case switching between generators |
83 | Figure A.12 – Time series of 3-phase voltages as RMSof change from generator stage 1 to stage 2 Figure A.13 – Time series of 3-phase currents as RMSof change from generator stage 1 to stage 2 Figure A.14 – Time series of active and reactive powerof change from generator stage 1 to stage 2 Figure A.15 – Time series of 3-phase voltages as RMSof change from generator stage 2 to stage 1 Figure A.16 – Time series of 3-phase currents as RMSof change from generator stage 2 to stage 1 |
84 | Figure A.17 – Time series of active and reactive powerof change from generator stage 2 to stage 1 Table A.9 – General test information Table A.10 – 95th percentile of 10-min harmonic magnitudes per power bin |
86 | Table A.11 – 95th percentile of 10-min harmonic magnitudes per power bin |
87 | Table A.12 – 95th percentile of 10-min harmonic magnitudes per power bin |
88 | A.4 Steady-state operation Figure A.18 – Max. of the 95th percentiles of integerharmonic currents vs. harmonic order Figure A.19 – Max. of the 95th percentiles ofinterharmonic currents vs. frequency Figure A.20 – Max. of the 95th percentiles of higherfrequency current components vs. frequency Table A.13 – Active power against wind speed (see 8.3.2) |
89 | Figure A.21 – Active power as a function of the wind speed Table A.14 – Measurement data set Table A.15 – Maximum active power |
90 | Figure A.22 – Reactive power vs. active power Table A.16 – Reactive power characteristic |
91 | Figure A.23 – PQ-Diagram Table A.17 – PQ-diagram |
92 | Figure A.24 – PQ-Diagram Table A.18 – PQ-diagram at maximum voltage |
93 | Figure A.25 – PQ-Diagram Table A.19 – PQ-diagram at minimum voltage Table A.20 – P-IUFi diagram |
94 | Figure A.26 – Mean 1-min current unbalance factor over active power Figure A.27 – Time-series of active power reference values, available power and measured active power output during active power control for the evaluation of the static error Figure A.28 – Time-series of measured wind speed during active power control during the test of the static error Table A.21 – General test information Table A.22 – Static error |
95 | Figure A.29 – Time-series of active power reference values, available power and measured active power output during active power control for the evaluation of the settling time Figure A.30 – Time-series of available and measured activepower output during ramp rate limitation Table A.23 – Dynamic response Table A.24 – General test information Table A.25 – Active power ramp rate calculation at start-up |
96 | Figure A.31 – Time-series of measured wind speed during ramp rate limitation Figure A.32 – Time-series of available and measured activepower output during ramp rate limitation Figure A.33 – Time-series of measured wind speed during ramp rate limitation Table A.26 – General test information Table A.27 – Active power ramp rate limitation at start-up |
97 | Figure A.34 – Time-series of available and measured activepower output during ramp rate limitation Figure A.35 – Time-series of measured wind speed during ramp rate limitation Table A.28 – General test information Table A.29 – Active power ramp rate limitation at normal stop Table A.30 – General test information |
98 | Figure A.36 – Time-series of available and measured activepower output during ramp rate limitation Figure A.37 – Time-series of measured wind speed during ramp rate limitation Table A.31 – Active power ramp rate limitation in normal operation Table A.32 – General test information |
99 | Figure A.38 – Time-series of available power, measured active powerand reference value of the grid frequency change Figure A.39 – Time-series of measured wind speed Figure A.40 – Measured active power over frequency change Table A.33 – Test at 0,25 × Pn < P < 0,5 × Pn |
100 | Figure A.41 – Time-series of available power, measured activepower and reference value of the grid frequency change Figure A.42 – Time-series of measured wind speed Figure A.43 – Measured active power over frequency change Table A.34 – Test at P > 0,8 x Pn |
101 | Figure A.44 – Test 1, time-series of available power, measured active power and reference value of the grid frequency for 0,25 × Pn < P < 0,5 × Pn Figure A.45 – Test 1, time-series of wind speed for 0,25 × Pn < P < 0,5 × Pn Table A.35 – Synthetic inertia results |
102 | Figure A.46 – Test 2, time-series of available power, measured active power and reference value of the grid frequency for 0,25 × Pn < P < 0,5 × Pn Figure A.47 – Test 2, time-series of wind speed for 0,25 × Pn < P < 0,5 × Pn Figure A.48 – Test 3, time-series of available power, measured active power and reference values of the grid frequency for P > 0,8 × Pn Figure A.49 – Test 3, time-series of wind speed for P > 0,8 × Pn Figure A.50 – Test 4, time-series of available power, measured active power and reference value of the grid frequency for P > 0,8 × Pn |
103 | Figure A.51 – Test 4, time-series of wind speed for P > 0,8 × Pn Figure A.52 – Test 5, time-series of available power, measured active power and reference value of the grid frequency for v > vn Figure A.53 – Test 5, time-series of wind speed for v > vn Figure A.54 – Test 6, time-series of available power, measured active power and reference value of the grid frequency for v > vn Figure A.55 – Test 6, time-series of wind speed for v > vn |
104 | Figure A.56 – Time-series of reactive power reference values and measured reactive power during the test of reactive power control Figure A.57 – Time-series of active power during the test of reactive power control Table A.36 – General test information Table A.37 – Static error |
105 | Figure A.58 – Time-series of reactive power reference values and measured reactive power during the test of reactive power dynamic response Figure A.59 – Time-series of active power during the testof reactive power dynamic response Table A.38 – Dynamic response |
106 | A.5 Dynamic performance (see 8.5) Figure A.60 – Wave shape of 3-phase voltages during entrance of voltage dip/swell when the WT under test is not connected Table A.39 – Results for tests where the WT is not connected |
107 | Figure A.61 – Wave shape of 3-phase voltages during clearance of voltage dip/swell when the WT under test is not connected Figure A.62 – 3-phase voltages as RMS (1 line period) duringthe test when the WT under test is not connected Figure A.63 – Positive sequence voltage during the test whenthe WT under test is not connected |
108 | Table A.40 – Results for tests where the WT is connected |
109 | Figure A.64 – Wave shape of 3-phase voltages during entranceof the voltage dip/swell when the WT under test is connected Figure A.65 – Wave shape of 3-phase voltages during clearanceof the voltage dip/swell when the WT under test is connected Figure A.66 – 3-phase voltages as RMS (1 line period) duringthe test when the WT under test is connected Figure A.67 – Positive and negative sequence fundamental voltage duringthe test when the WT under test is connected Figure A.68 – 3-phase currents as RMS (1 line period) duringthe test when the WT under test is connected |
110 | Figure A.69 – Pos. and neg. sequence fundamental current duringthe test when the WT under test is connected Figure A.70 – Pos. sequence fundamental active power duringthe test when the WT under test is connected. Figure A.71 – Pos. sequence fundamental reactive power duringthe test when the WT under test is connected Figure A.72 – Pos. sequence fundamental active current duringthe test when the WT under test is connected Figure A.73 – Pos. sequence fundamental reactive current duringthe test when the WT under test is connected |
111 | A.6 Disconnection from grid (see 8.6) Figure A.74 – Wind speed or available power during the test whenthe WT under test is connected Table A.41 – Voltage protection Table A.42 – Frequency protection Table A.43 – Complete trip circuit test |
112 | Figure A.75 – Voltage during the reconnection test of 10 s Figure A.76 – Active power during the reconnection test of 10 s, including the recovery Table A.44 – RoCoF test results Table A.45 – RoCoF test information Table A.46 – Reconnection test results |
113 | Figure A.77 – Time-series of measured wind speed during the reconnection test of 10 s Figure A.78 – Voltage during the reconnection test of 60 s Figure A.79 – Active power during the reconnection test of 60 s, including the recovery Figure A.80 – Time-series of measured wind speed during the reconnection test of 60 s Figure A.81 – Voltage during the reconnection test of 600 s |
114 | Figure A.82 – Active power during the reconnection test of 600 s including the recovery Figure A.83 – Time-series of measured wind speed during the reconnection test of 600 s |
115 | Annex B (informative)Voltage fluctuations and flicker B.1 Continuous operation B.2 Switching operations Figure B.1 – Measurement procedure for flicker duringcontinuous operation of the wind turbine |
116 | B.3 Verification test of the measurement procedure for flicker B.3.1 General Figure B.2 – Measurement procedure for voltage changes and flickerduring switching operations of the wind turbine Table B.1 – Nominal values of the wind turbine usedin the verification tests |
117 | B.3.2 Fictitious grid performance testing Table B.2 – Input relative current fluctuation, ΔI/I, for flicker coefficientc((ψk) = 2,00 ( 5 % when Sk,fic = 20·Sn Table B.3 – Input relative current fluctuation, ΔI/I, for flicker coefficientc((ψk) = 2,00 ( 5 % when Sk,fic = 50·Sn |
118 | B.3.3 Distorted um(t) voltage with multiple zero crossings B.3.4 Distorted um(t) voltage with inter-harmonic modulation Table B.4 – Test specification for distorted voltage with multiple zero crossings |
119 | B.3.5 Slow frequency changes B.4 Deduction of definitions B.4.1 Flicker coefficient |
120 | B.4.2 Flicker step factor |
121 | B.4.3 Voltage change factor |
122 | Annex C (normative)Measurement of active power, reactive power and voltage C.1 General C.2 Generator convention of the signs Figure C.1 – Positive directions of active power, reactive power, instantaneous phase voltages and instantaneous phase currents with generator convention |
123 | C.3 Calculation of positive, negative and zero sequence quantities C.3.1 Phasor calculations Figure C.2 – Examples of the power phasor diagrams of the generator convention in each quadrant with respective instantaneous phase voltage and current |
126 | C.3.2 Calculation of the positive sequence quantities using phasor components |
127 | C.3.3 Calculation of the negative sequence quantities using phasor components |
128 | C.3.4 Calculation of the zero sequence quantities using phasor components |
130 | Annex D (informative)Harmonic evaluation D.1 General D.2 General analysis methods D.2.1 General D.2.2 Harmonic voltages D.2.3 Harmonic phase angles and magnitudes |
131 | Figure D.1 – Definition of the phase angles of the spectral line in generator convention – (5th harmonic with αI5 = + 120° and αU5 = + 170°shown as an example, thus 5th harmonic phase angle is φ5 = + 170° − 120° = + 50°) |
132 | Figure D.2 – Comparison of harmonic amplitude aggregation (dotted) no aggregated amplitude directly from DFT with 10-cycle window, (dashed) 10-second aggregation |
133 | Figure D.3 – Comparison of the prevailing angle ratio (PAR) |
134 | D.2.4 Statistical analysis D.2.5 Sample rate adjustment D.2.6 Determination of background harmonic voltage distortion D.2.7 Diurnal variations of the harmonic voltage and current |
135 | D.2.8 Shutting down neighbouring WT or loads D.2.9 Harmonics of current and voltage over power |
136 | D.2.10 Filters switching |
137 | D.2.11 Measuring at a standard source D.2.12 Harmonics power flow + voltage measurement, phase angle |
138 | D.2.13 Voltage harmonics with and without operation of the tested wind turbine Table D.1 – Example of measurements results presentation |
139 | D.2.14 Measurements at different sites D.2.15 Harmonic model D.3 Determination of harmonic amplitude affected by space harmonics at DFAG systems |
141 | Annex E (informative)Assessment of power quality of wind turbines and wind power plants E.1 General E.2 Voltage fluctuations E.2.1 General |
142 | E.2.2 Continuous operation E.2.3 Switching operations |
143 | E.3 Current harmonics, interharmonics and higher frequency components |
144 | Table E.1– Specification of exponents in accordance with IEC TR 61000-3-6 |
145 | Annex F (informative)Guidelines for the transferability of test results to different turbine variants in the same product platform |
146 | Figure F.1 – Block diagram for generic wind turbine (source IEC 61400-27-1) |
147 | Table F.1– Main components influencing the electrical characteristics of the WT |
149 | Bibliography |