BS EN IEC 62271-202:2022 – TC
$280.87
Tracked Changes. High-voltage switchgear and controlgear – AC prefabricated substations for rated voltages above 1 kV and up to and including 52 kV
Published By | Publication Date | Number of Pages |
BSI | 2022 | 312 |
This part of IEC 62271 specifies the service conditions, rated characteristics, general structural requirements and test methods of enclosed high-voltage prefabricated substations. These prefabricated substations are cable-connected to AC high-voltage networks with an operating voltage up to and including 52 kV and power frequencies up to and including 60 Hz. They can be manually operated from inside (walk-in type) or from outside (non-walk-in type). They are designed for outdoor installation at locations with public accessibility and where protection of personnel is provided. These prefabricated substations can be situated at ground level or partially or completely below ground level. The last are also called “underground prefabricated substations”. In general, two types of prefabricated substations are considered in this document: – high-voltage switchgear prefabricated substations; – high-voltage/low-voltage transformer prefabricated substations (step-up and step-down). A high-voltage switchgear prefabricated substation comprises an enclosure containing in general the following electrical components: – high-voltage switchgear and controlgear; – auxiliary equipment and circuits. A high-voltage/low-voltage transformer prefabricated substation comprises an enclosure containing in general the following electrical components: – power transformer(s); – high-voltage and low-voltage switchgear and controlgear; – high-voltage and low-voltage interconnections; – auxiliary equipment and circuits. However, relevant provisions of this document are applicable to designs where not all these electrical components exist (for example, a prefabricated substation consisting of power transformer and low-voltage switchgear and controlgear). The listed electrical components of a high-voltage/low-voltage transformer prefabricated substation can be incorporated in the prefabricated substation either as separate components or as an assembly type CEADS according to IEC 62271-212. This document covers only designs using natural ventilation. However, relevant provisions of this document are applicable to designs using other means of ventilation except the rated power of the prefabricated substation and associated class of enclosure (see 5.101), the continuous current tests (see 7.5) and all temperature rise related requirements, which would need an agreement between manufacturer and user. NOTE 1 IEC 61936-1 [1]1 provides general rules for the design and erection of high-voltage power installations. As well, it specifies additional requirements for the external connections, erection and operation at the place of installation of high-voltage prefabricated substations compliant with IEC 62271-202, which are regarded as a component of such installation. Non-prefabricated high-voltage substations, are generally covered by IEC 61936-1 [1]. NOTE 2 High-voltage switchgear prefabricated substations can include instrument transformers, according to IEC 61869 (all parts). These substations are not high-voltage/low-voltage transformer prefabricated substations.
PDF Catalog
PDF Pages | PDF Title |
---|---|
1 | 30462301 |
187 | A-30408461 |
188 | undefined |
192 | Annex ZA (normative)Normative references to international publicationswith their corresponding European publications |
195 | English CONTENTS |
202 | FOREWORD |
204 | INTRODUCTION |
205 | 1 Scope |
206 | 2 Normative references |
208 | 3 Terms and definitions 3.1 General terms and definitions 3.2 Assemblies of switchgear and controlgear 3.3 Parts of assemblies |
209 | 3.4 Switching devices |
210 | 3.5 Parts of switchgear and controlgear 3.6 Operational characteristics of switchgear and controlgear |
211 | 3.7 Characteristic quantities 3.8 Index of definitions 4 Normal and special service conditions 4.1 Normal service conditions 4.1.1 General |
212 | 4.1.2 Indoor switchgear and controlgear 4.1.3 Outdoor switchgear and controlgear 4.1.101 Low-voltage switchgear and controlgear 4.1.102 Power transformer |
213 | 4.2 Special service conditions 4.2.1 General 4.2.2 Altitude 4.2.3 Exposure to pollution |
214 | 4.2.4 Temperature and humidity 4.2.5 Exposure to abnormal vibrations, shock or tilting 4.2.6 Wind speed 4.2.7 Other parameters 5 Ratings 5.1 General |
215 | 5.2 Rated voltage (Ur) 5.3 Rated insulation level (Ud, Up, Us) |
216 | 5.4 Rated frequency (fr) 5.5 Rated continuous current (Ir) 5.6 Rated short-time withstand current (Ik) 5.6.101 Rated short-time withstand current of high-voltage switchgear and controlgear and high-voltage interconnection (Ik) |
217 | 5.6.102 Rated short-time phase to earth withstand current (Ike) 5.6.103 Rated short-time withstand currents of low-voltage switchgear and controlgear and low-voltage interconnection (Icw) 5.7 Rated peak withstand current (Ip) 5.7.101 Rated peak phase to earth withstand current (Ipe) 5.7.102 Rated peak withstand currents of low-voltage switchgear and controlgear and low-voltage interconnection (Ipk) 5.8 Rated duration of short-circuit (tk) |
218 | 5.8.101 Rated duration of short-circuit (tk) 5.8.102 Rated duration of phase to earth short-circuit (tke) 5.8.103 Rated duration of short-circuits for low-voltage switchgear and controlgear and low-voltage interconnection 5.8.104 Rated duration of short-circuits for power transformers 5.9 Rated supply voltage of auxiliary and control circuits (Ua) 5.10 Rated supply frequency of auxiliary and control circuits 5.11 Rated pressure of compressed gas supply for controlled pressure systems 5.101 Rated power of prefabricated substation and class of enclosure 5.101.1 Rated power of the prefabricated substation |
219 | 5.101.2 Rated class of enclosure 5.102 Ratings of the internal arc classification (IAC) 5.102.1 General 5.102.2 Types of accessibility (A, B, AB) |
220 | 5.102.3 Rated arc fault currents (IA, IAe) 5.102.4 Rated arc fault duration (tA, tAe) 6 Design and construction |
221 | 6.1 Requirements for liquids in switchgear and controlgear 6.2 Requirements for gases in switchgear and controlgear 6.3 Earthing of switchgear and controlgear |
222 | 6.4 Auxiliary and control equipment and circuits 6.4.1 General 6.4.2 Protection against electric shock |
223 | 6.4.3 Components installed in enclosures 6.5 Dependent power operation 6.6 Stored energy operation |
224 | 6.7 Independent unlatched operation (independent manual or power operation) 6.8 Manually operated actuators 6.9 Operation of releases 6.10 Pressure/level indication 6.11 Nameplates 6.12 Locking devices 6.13 Position indication 6.14 Degrees of protection provided by enclosures |
225 | 6.15 Creepage distances for outdoor insulators 6.16 Gas and vacuum tightness 6.17 Tightness for liquid systems 6.18 Fire hazard (flammability) 6.19 Electromagnetic compatibility (EMC) 6.20 X-ray emission 6.21 Corrosion 6.22 Filling levels for insulation, switching and/or operation |
226 | 6.101 Protection of the prefabricated substation against mechanical stress 6.102 Protection of the environment due to internal defects |
227 | 6.103 Internal arc fault 6.104 Enclosure 6.104.1 General |
228 | 6.104.2 Fire behaviour Table 1 – Synthetic material characteristics |
229 | 6.104.3 Environmental considerations 6.104.4 Covers and doors |
230 | 6.104.5 Ventilation openings 6.104.6 Partitions 6.105 Other provisions 6.105.1 Provisions for dielectric tests on cables 6.105.2 Accessories |
231 | 6.105.3 Operation aisle 6.105.4 Labels 6.105.5 Provisions for on-site assembly of prefabricated substation 6.106 Sound emission 6.107 Electromagnetic fields 6.108 Solar radiation |
232 | 7 Type tests 7.1 General 7.1.1 Basics |
233 | 7.1.2 Information for identification of test objects 7.1.3 Information to be included in type-test reports 7.2 Dielectric tests 7.2.1 General Table 2 – Type tests |
234 | 7.2.2 Ambient air conditions during tests 7.2.3 Wet test procedure 7.2.4 Arrangement of the equipment 7.2.5 Criteria to pass the test 7.2.6 Application of the test voltage and test conditions 7.2.7 Tests of switchgear and controlgear of Ur ≤ 245 kV 7.2.8 Tests of switchgear and controlgear of Ur > 245 kV 7.2.9 Artificial pollution tests for outdoor insulators 7.2.10 Partial discharge tests 7.2.11 Dielectric tests on auxiliary and control circuits |
235 | 7.2.12 Voltage test as condition check 7.2.101 Tests on the high-voltage components |
236 | 7.2.102 Tests on low-voltage interconnection |
237 | 7.3 Radio interference voltage (RIV) test 7.4 Resistance measurement 7.4.1 Measurement of the resistance of auxiliary contacts class 1 and class 2 7.4.2 Measurement of the resistance of auxiliary contacts class 3 7.4.3 Electrical continuity of earthed metallic parts test |
238 | 7.4.4 Resistance measurement of contacts and connections in the main circuit as a condition check 7.5 Continuous current tests 7.5.101 General |
239 | 7.5.102 Test conditions Figure 1 – Measurement of power transformer temperature rise in ambient air: ∆t1 Figure 2 – Measurement of power transformer temperature rise in an enclosure: ∆t2 |
240 | 7.5.103 Test methods |
241 | Figure 3 – Diagram of the preferred continuous current test method |
242 | Figure 4 – Diagram of the continuous current test alternative method |
243 | Figure 5 – Diagram for open-circuit test |
244 | 7.5.104 Measurements |
246 | 7.5.105 Acceptance criteria Figure 6 – Example of air temperature measurement locationsinside a non-walk-in type prefabricated substation |
247 | 7.5.106 Continuous current test under solar radiation 7.6 Short-time withstand current and peak withstand current tests |
248 | 7.7 Verification of the protection 7.8 Tightness tests 7.9 Electromagnetic compatibility tests (EMC) 7.10 Additional tests on auxiliary and control circuits 7.10.1 General 7.10.2 Functional tests |
249 | 7.10.3 Verification of the operational characteristics of auxiliary contacts 7.10.4 Environmental tests 7.10.5 Dielectric test 7.11 X-radiation test for vacuum interrupters 7.101 Calculations and mechanical tests 7.101.1 Wind pressure 7.101.2 Roof loads 7.101.3 Mechanical impacts 7.101.4 Handling |
250 | 7.102 Internal arc test 7.102.1 General 7.102.2 Test conditions |
251 | 7.102.3 Arrangement of the equipment 7.102.4 Test procedure 7.102.5 Criteria to pass the test |
253 | 7.102.6 Test report 7.102.7 Transferability of tests results |
254 | 7.103 Measurement or calculation of electromagnetic fields 8 Routine tests 8.1 General 8.2 Dielectric test on the main circuit 8.3 Test on auxiliary and control circuits 8.3.1 Inspection of auxiliary and control circuits, and verification of conformity to the circuit diagrams and wiring diagrams 8.3.2 Functional tests 8.3.3 Verification of protection against electric shock |
255 | 8.3.4 Dielectric tests 8.4 Measurement of the resistance of the main circuit 8.5 Tightness test 8.6 Design and visual checks 8.101 Other functional tests 8.102 Tests after assembly on site 9 Guide to the selection of switchgear and controlgear (informative) 9.101 General |
256 | 9.102 Selection of rated values 9.103 Selection of class of enclosure |
257 | 9.104 Internal arc fault 9.104.1 General 9.104.2 Causes and preventive measures 9.104.3 Supplementary protective measures |
258 | Table 3 – Locations, causes and examples of measures decreasingthe probability of internal arcs |
259 | 9.104.4 Considerations for the selection and installation 9.104.5 IAC classification |
260 | 9.105 Summary of technical requirements and ratings Table 4 – Single phase-to-earth arc fault current dependingon the network neutral earthing |
261 | Table 5 – Summary of technical requirements, characteristicsand ratings relevant for prefabricated substations |
266 | 10 Information to be given with enquiries, tenders and orders (informative) 10.1 General 10.2 Information with enquiries and orders |
267 | 10.3 Information with tenders 11 Transport, storage, installation, operating instructions and maintenance 11.1 General |
268 | 11.2 Conditions during transport, storage and installation 11.3 Installation 11.3.1 General 11.3.2 Unpacking and lifting 11.3.3 Assembly 11.3.4 Mounting |
269 | 11.3.5 Connections 11.3.6 Information about gas and gas mixtures for controlled and closed pressure systems 11.3.7 Final installation inspection 11.3.8 Basic input data by the user 11.3.9 Basic input data by the manufacturer 11.4 Operating instructions 11.5 Maintenance |
270 | 12 Safety 12.101 General 12.102 Electrical aspects 12.103 Mechanical aspects 12.104 Thermal aspects 12.105 Internal arc aspects 13 Influence of the product on the environment |
271 | Annex A (normative)Internal arc fault – Method to verify the internal arc classification (IAC) A.1 General A.2 Room simulation A.3 Indicators (for assessing the thermal effects of the gases) A.3.1 General |
272 | Figure A.1 – Mounting frame for vertical indicators Figure A.2 – Horizontal indicators |
273 | A.3.2 Arrangement of indicators |
279 | A.4 Tolerances for geometrical dimensions of test arrangements A.5 Test parameters Figure A.3 – Arrangement of indicators |
280 | A.6 Test procedure Figure A.4 – Selection of tests on high-voltage switchgearand controlgear for class IAC-A |
281 | Figure A.5 – Selection of tests on high-voltage switchgearand controlgear for class IAC-B |
282 | Figure A.6 – Selection of tests on high-voltage interconnections for class IAC-A |
283 | Figure A.7 – Selection of tests on high-voltage interconnections for class IAC-B |
285 | Annex B (normative)Test to verify the sound level of a high-voltage/low-voltagetransformer prefabricated substation B.1 Purpose B.2 Test object B.3 Test method B.4 Measurements B.5 Presentation and calculation of the results |
287 | Annex C (normative)Mechanical impact test C.1 Test for the verification of the resistance to mechanical impact C.2 Apparatus for the verification of the protection against mechanical damage |
288 | Figure C.1 – Impact test apparatus |
289 | Annex D (informative)Rating of power transformers in an enclosure D.1 General D.2 Mineral-oil-immersed power transformer |
290 | D.3 Dry-type power transformer Figure D.1 – Mineral-oil-immersed power transformer load factor inside of the enclosure related to ambient air at the location and top-oil and winding temperature rise limits Figure D.2 – Dry-type power transformer load factor outside of the enclosure |
291 | Figure D.3 – Insulation class 105 °C (A) dry-type powertransformers load factor in an enclosure |
292 | Figure D.4 – Insulation class 120 °C (E) dry-type powertransformers load factor in an enclosure Figure D.5 – Insulation class 130 °C (B) dry-type powertransformers load factor in an enclosure |
293 | Figure D.6 – Insulation class 155 °C (F) dry-type powertransformers load factor in an enclosure Figure D.7 – Insulation class 180 °C (H) dry-type powertransformers load factor in an enclosure |
294 | D.4 Example Figure D.8 – Insulation class 200 °C (H) dry-type powertransformers load factor in an enclosure Figure D.9 – Insulation class 220 °C (H) dry-type powertransformers load factor in an enclosure |
297 | Annex E (informative)Examples of earthing arrangements Figure E.1 – Example of earthing arrangement |
298 | Figure E.2 – Example of earthing arrangement |
299 | Figure E.3 – Example with the framework serving as part of the main earthing conductor |
300 | Annex F (informative)Characteristics of enclosure materials F.1 Metals F.1.1 Coatings F.1.2 Paints F.2 Concrete Table F.1 – Treatment of coatings Table F.2 – Tests of coatings |
301 | Table F.3 – Test of concrete |
302 | Annex G (informative)Evaluation of the impact of solar radiation –Simulated solar radiation continuous current test G.1 General G.2 Test method G.2.1 General G.2.2 Test parameters, equipment and preparation |
303 | Figure G.1 – Indicative arrangement of laboratory radiation sources (e.g. radiant heat lamps) for continuous current test with simulated solar radiation |
304 | G.2.3 Test procedure and application of test currents G.2.4 Measurements |
305 | G.3 Evaluation of the solar radiation effects G.3.1 Evaluation of solar radiation effects on the temperature rise of power transformer G.3.2 Evaluation of solar radiation effects on the temperature rise of components other than the power transformer G.4 Application considerations |
307 | Annex H (informative)Installation conditions of electronic equipment H.1 General H.2 Accessibility |
308 | H.3 Application of air temperature measurements inside the prefabricated substation |
309 | Bibliography |