Shopping Cart

No products in the cart.

BSI PD IEC/TR 62271-306:2012+A1:2018

$215.11

High-voltage switchgear and controlgear – Guide to IEC 62271-100, IEC 62271-1 and other IEC standards related to alternating current circuit-breakers

Published By Publication Date Number of Pages
BSI 2018 384
Guaranteed Safe Checkout
Categories: ,

If you have any questions, feel free to reach out to our online customer service team by clicking on the bottom right corner. Weโ€™re here to assist you 24/7.
Email:[email protected]

This part of IEC 62271 is applicable to a.c. circuit-breakers designed for indoor or outdoor installation and for operation at frequencies of 50 Hz and 60 Hz on systems having voltages above 1 000 V.

NOTE While this technical report mainly addresses circuit-breakers, some clauses (e.g. Clause 5) apply to switchgear and controlgear.

This technical report addresses utility, consultant and industrial engineers who specify and apply high-voltage circuit-breakers, circuit-breaker development engineers, engineers in testing stations, and engineers who participate in standardization. It is intended to provide background information concerning the facts and figures in the standards and provide a basis for specification for high-voltage circuit-breakers. Thus, its scope will cover the explanation, interpretation and application of IEC 62271-100 and IEC 62271-1 as well as related standards and technical reports with respect to high-voltage circuit-breakers.

Rules for circuit-breakers with intentional non-simultaneity between the poles are covered by IEC 62271-302.

This technical report does not cover circuit-breakers intended for use on motive power units of electrical traction equipment; these are covered by the IEC 60077 series.

Generator circuit-breakers installed between generator and step-up transformer are not within the scope of this technical report.

This technical report does not cover self-tripping circuit-breakers with mechanical tripping devices or devices which cannot be made inoperative.

Disconnecting circuit-breakers are covered by IEC 62271-108.

By-pass switches in parallel with line series capacitors and their protective equipment are not within the scope of this technical report. These are covered by IEC 62271-109 and IEC 60143-2.

In addition, special applications (among others parallel switching, delayed current zero crossings) are treated in annexes to this document.

PDF Catalog

PDF Pages PDF Title
2 undefined
19 1.1 Scope
1.2 Normative references
24 3.1 General
3.2 Electrical endurance class E1 and E2
25 3.3 Capacitive current switching class C1 and C2
3.4 Mechanical endurance class M1 and M2
26 3.5 Class S1 and S2
3.6 Conclusion
27 4.1 General
30 Table 1 โ€“ Classes and shapes of stressing voltages and overvoltages (from IEC 60071-1:2006, Table 1)
31 4.2 Longitudinal voltage stresses
4.3 High-voltage tests
32 4.4 Impulse voltage withstand test procedures
33 Table 2 โ€“ 15/2 and 3/9 test series attributes
34 Figure 1 โ€“ Probability of acceptance (passing the test) for the 15/2 and 3/9 test series
35 Figure 2 โ€“ Probability of acceptance at 5 % probability of flashover for 15/2 and 3/9 test series
Figure 3 โ€“ User risk at 10 % probability of flashover for 15/2 and 3/9 test series
38 Figure 4 โ€“ Operating characteristic curves for 15/2 and 3/9 test series
39 Figure 5 โ€“ ฮฑ risks for 15/2 and 3/9 test methods
Table 3 โ€“ Summary of theoretical analysis
40 4.5 Correction factors
Figure 6 โ€“ ฮฒ risks for 15/2 and 3/9 test methods
Figure 7 โ€“ Ideal sampling plan for AQL of 10 %
41 Table 4 โ€“ Values for m for the different voltage waveshapes
44 4.6 Background information about insulation levels and tests
Figure 8 โ€“ Disruptive discharge mode of external insulation of switchgear and controlgear having a rated voltage above 1 kV up to and including 52 kV
47 4.7 Lightning impulse withstand considerations of vacuum interrupters
48 5.1 General
5.2 Load current carrying requirements
52 5.3 Temperature rise testing
Table 5 โ€“ Maximum ambient temperature versus altitude (IEC 60943)
53 Table 6 โ€“ Some examples of the application of acceptance criteria for steady state conditions
54 Figure 9 โ€“ Temperature curve and definitions
Figure 10 โ€“ Evaluation of the steady state condition for the last quarter of the test duration shown in Figure 9
55 5.4 Additional information
Table 7 โ€“ Ratios of Ia/Ir for various ambient temperatures based on Table 3 of IEC 62271-1:2007
56 6.1 Harmonization of IEC and IEEE transient recovery voltages
59 Figure 11 โ€“ Comparison of IEEE, IEC and harmonized TRVs, example for 145 kV at 100 % Isc with kpp = 1,3
60 Table 8 โ€“ Summary of recommended changes to harmonize IEC and IEEE TRV requirements
Table 9 โ€“ Recommended u1 values
62 Figure 12 โ€“ Comparison of IEEE, IEC and harmonized TRVs with compromise values of u1 and t1, example for 145 kV at 100 % Isc with kpp = 1,3
64 Figure 13 โ€“ Comparison of TRVโ€™s for cable-systems and line-systems
65 6.2 Initial Transient Recovery Voltage (ITRV)
Figure 14 โ€“ Harmonization of TRVs for circuit-breakers < 100 kV
67 Figure 15 โ€“ Representation of ITRV and terminal fault TRV
68 6.3 Testing
Table 10 โ€“ Standard values of initial transient recovery voltage โ€“ Rated voltages 100 kV and above
69 Figure 16 โ€“ Typical graph of line side TRV with time delay and source side with ITRV
70 6.4 General considerations regarding TRV
71 Figure 96 โ€“ Representation of a four-parameter TRV and a delay line
72 Figure 97 โ€“ Representation of a specified TRV by a two-parameter reference line and a delay line
74 Table 39 โ€“ First-pole-to-clear factors kpp
75 Table 40 โ€“ Pole-to-clear factors for each clearing pole
76 Table 41 โ€“ Pole-to-clear factors for other types of faults in non-effectively earthed neutral systems
81 6.5 Calculation of TRVs
83 7.1 Short-line fault requirements
88 7.2 SLF testing
91 7.3 Additional explanations on SLF
93 Figure 17 โ€“ Effects of capacitor size on the short-line fault component of recovery voltage with a fault 915 m from circuit-breaker
94 Figure 18 โ€“ Effect of capacitor location on short-line fault component of transient recovery voltage with a fault 760 m from circuit-breaker
95 Figure 19 โ€“ TRV obtained during a L90 test duty on a 145 kV, 50 kA, 60 Hz circuit-breaker
96 7.4 Comparison of surge impedances
7.5 Test current and line length tolerances for short-line fault testing
Table 11 โ€“ Comparison of typical values of surge impedances for a single-phase fault (or third pole to clear a three-phase fault) and the first pole to clear a three-phase fault
97 7.6 TRV with parallel capacitance
Table 42 โ€“ Actual percentage short-line fault breaking currents
100 8.1 Reference system conditions
Figure 20 โ€“ TRV vs. ฯ‰IZ as function of t/tdL when tL/tdL = 4,0
101 Figure 21 โ€“ Typical system configuration for out-of-phase breaking for case A
Figure 22 โ€“ Typical system configuration for out-of-phase breaking for Case B
102 8.2 TRV parameters introduced into Tables 1b and 1c of the first edition of IEC 62271-100
104 Figure 23 โ€“ Voltage on both sides during CO under out-of-phase conditions
Figure 24 โ€“ Fault currents during CO under out-of-phase
Figure 25 โ€“ TRVs for out-of-phase clearing (enlarged)
105 9.1 General
106 9.2 General theory of capacitive current switching
Figure 98 โ€“ Single-phase equivalent circuit for capacitive current interruption
107 Figure 99 โ€“ Voltage and current shapes at capacitive current interruption
108 Figure 100 โ€“ Voltage and current wave shapes in the case of a restrike
109 Figure 101 โ€“ Voltage build-up by successive restrikes
110 Figure 102 โ€“ Example of an NSDD during capacitive current interruption
111 Figure 103 โ€“ Recovery voltage of the first-pole-to-clear at interruption of a three-phase non-effectively earthed capacitive load
112 9.3 Capacitor bank switching
Figure 104 โ€“ General circuit for capacitor bank switching
115 9.4 No-load cable switching
116 Figure 105 โ€“ Typical circuit for no-load cable switching
117 Figure 106 โ€“ Individually screened cable with equivalent circuit
Figure 107 โ€“ Belted cable with equivalent circuit
118 Figure 108 โ€“ Cross-section of a high-voltage cable
122 Figure 109 โ€“ Equivalent circuit for back-to-back cable switching
123 Figure 110 โ€“ Equivalent circuit of a compensated cable
125 Figure 111 โ€“ Currents when making at voltage maximum and full compensation
126 Figure 112 โ€“ Currents when making at voltage zero and full compensation
127 Figure 113 โ€“ Currents when making at voltage maximum and partial compensation
Figure 114 โ€“ Currents when making at voltage zero and partial compensation
129 9.5 No-load transmission line switching
Figure 115 โ€“ RMS charging current versus system voltage for different line configurations at 60 Hz
130 Figure 116 โ€“ General circuit for no-load transmission line switching
131 Figure 117 โ€“ Recovery voltage peak in the first-pole-to-clear as a function of C1/C0, delayed interruption of the second phase
133 Figure 118 โ€“ Typical current and voltage relations for a compensated line
Figure 119 โ€“ Half cycle of recovery voltage
134 Figure 120 โ€“ Energisation of no-load lines: basic phenomena
135 9.6 Voltage factors for capacitive current switching tests
Table 43 โ€“ Voltage factors for single-phase capacitive current switching tests
136 Figure 121 โ€“ Recovery voltage on first-pole-to-clear for three-phase interruption: capacitor bank with isolated neutral
137 9.7 General application considerations
138 Figure 122 โ€“ Example of the recovery voltage across a filter bank circuit-breaker
142 Table 44 โ€“ Inrush current and frequency for switching capacitor banks
143 Table 45 โ€“ Typical values of inductance between capacitor banks
144 Figure 123 โ€“ Typical circuit for back-to-back switching
145 Figure 124 โ€“ Example of 123 kV system
149 Figure 125 โ€“ Voltage and current relations for capacitor switching through interposed transformer
151 Figure 126 โ€“ Station illustrating large transient inrush currents through circuit-breakers from parallel capacitor banks
155 9.8 Considerations of capacitive currents and recovery voltages under fault conditions
156 Figure 127 โ€“ Fault in the vicinity of a capacitor bank
157 Figure 128 โ€“ Recovery voltage and current for first-phase-to-clear when the faulted phase is the second phase-to-clear
Figure 129 โ€“ Recovery voltage and current for last-phase-to-clear when the faulted phase is the first-phase-to-clear
158 Figure 130 โ€“ Basic circuit for shunt capacitor bank switching
159 9.9 Explanatory notes regarding capacitive current switching tests
161 10.1 Specification
162 10.2 Testing
163 Figure 131 โ€“ Example of a tightness coordination chart, TC, for closed pressure systems
164 Table 46 โ€“ Sensitivity and applicability of different leak-detection methods for tightness tests
169 Table 47 โ€“ Results of a calibration procedure prior to a low temperature test
170 10.3 Cumulative test method and calibration procedure for type tests on closed pressure systems
173 Table 16 โ€“ Results of the calibration of the enclosure
174 11.1 Energy for operation to be used during demonstration of the rated operating sequence during short-circuit making and breaking tests
175 11.2 Alternative operating mechanisms
176 Figure 64 โ€“ Comparison of reference and alternative mechanical characteristics
177 Figure 65 โ€“ Closing operation outside the envelope
178 Figure 66 โ€“ Mechanical characteristics during a T100s test
180 12.1 General
181 12.2 Basic considerations
182 12.3 Applicability of type tests at different frequencies
183 Table 17 โ€“ Temperature rise tests
Table 18 โ€“ Short-time withstand current tests
Table 19 โ€“ Peak withstand current tests
Table 20 โ€“ Short-circuit making current tests
184 Table 21 โ€“ Terminal faults: symmetrical test duties
Table 22 โ€“ Terminal faults: asymmetrical test duties
Table 23 โ€“ Short-line faults
Table 24 โ€“ Capacitive current switching
185 13.1 General
13.2 Arcing time
13.3 Symmetrical currents
187 Figure 132 โ€“ Interrupting windows and kp value for three-phase fault in a non effectively earthed system
188 Figure 133 โ€“ Three-phase unearthed fault current interruption
189 Figure 134 โ€“ Interrupting windows and kp values for three-phase fault to earth in an effectively earthed system at 800 kV and below
Figure 135 โ€“ Interrupting windows and kp values for three-phase fault to earth in an effectively earthed system above 800 kV
190 Figure 136 โ€“ Simulation of three-phase to earth fault current interruption at 50 Hz
192 13.4 Asymmetrical currents
Table 48 โ€“ Example of comparison of rated values against application (Ur = 420 kV)
194 Figure 137 โ€“ Case 1 with interruption by a first pole (blue phase) after minor loop of current with intermediate asymmetry
195 Figure 138 โ€“ Case 2 with interruption of a last pole-to-clear after a major extended loop of current with required asymmetry and longest arcing time
196 Figure 139 โ€“ Case 3 with interruption of a last pole-to-clear after a major extended loop of current with required asymmetry but not the longest arcing time
Figure 140 โ€“ Case 4 with interruption by the first pole in the red phase after a major loop of current with required asymmetry and the longest arcing time (for a first-pole-to-clear)
198 13.5 Double earth fault
199 Figure 141 โ€“ Representation of a system with a double earth fault
200 Figure 142 โ€“ Representation of circuit with double-earth fault
202 Figure 143 โ€“ Fault currents relative to the three-phase short-circuit current
203 13.6 Break time
204 14.1 General
Figure 144 โ€“ Principle of synthetic testing
205 14.2 Current injection methods
Figure 145 โ€“ Typical current injection circuit with voltage circuit in parallel with the test circuit-breaker
206 Figure 146 โ€“ Injection timing for current injection scheme with the circuit given in Figure 145
207 Figure 147 โ€“ Examples of the determination of the interval of significant change of arc voltage from the oscillograms
208 14.3 Duplicate transformer circuit
Figure 148 โ€“ Transformer or Skeats circuit
210 14.4 Voltage injection methods
Figure 149 โ€“ Triggered transformer or Skeats circuit
211 Figure 150 โ€“ Typical voltage injection circuit diagram with voltage circuit in parallel with the auxiliary circuit-breaker (simplified diagram)
212 Figure 151 โ€“ TRV waveshapes in a voltage injection circuit with the voltage circuit in parallel with the auxiliary circuit-breaker
213 14.5 Current distortion
214 Figure 152 โ€“ Direct test circuit, simplified diagram
Figure 153 โ€“ Prospective short-circuit current flow
Figure 154 โ€“ Distortion current flow
215 Figure 155 โ€“ Distortion current
216 Figure 156 โ€“ Simplified circuit diagram for high-current interval
218 Figure 157 โ€“ Current and arc voltage characteristics for symmetrical current and constant arc voltage
219 Figure 158 โ€“ Current and arc voltage characteristics for asymmetrical current and constant arc voltage
220 Figure 159 โ€“ Reduction of amplitude and duration of final current loop of arcing for symmetrical current and constant arc voltage
221 Figure 160 โ€“ Reduction of amplitude and duration of final current loop of arcing for symmetrical current and linearly rising arc voltage
222 Figure 161 โ€“ Reduction of amplitude and duration of final current loop of arcing for asymmetrical current and constant arc voltage
223 Figure 162 โ€“ Reduction of amplitude and duration of final current loop of arcing for asymmetrical current and linearly rising arc voltage
228 14.6 Step-by-step method to prolong arcing
Figure 163 โ€“ Typical re-ignition circuit diagram for prolonging arc-duration
229 14.7 Examples of the application of the tolerances on the last current loop based on 4.1.2 and 6.109 of IEC 62271-101:2012
Figure 164 โ€“ Typical waveshapes obtained during a symmetrical test using the circuit in Figure 163
230 15.1 General
15.2 Transport and storage
231 15.3 Installation
15.4 Commissioning
233 15.5 Operation
15.6 Maintenance
15.7 Corrosion: Information regarding service conditions and recommended test requirements
234 15.8 Electromagnetic compatibility on site
235 16.1 General
236 16.2 Shunt reactor switching
Figure 75 โ€“ General case for shunt reactor switching
237 Figure 76 โ€“ Current chopping phenomena
238 Figure 77 โ€“ General case first-pole-to-clear representation
239 Figure 78 โ€“ Single phase equivalent circuit for the first-pole-to-clear
240 Figure 79 โ€“ Voltage conditions at and after current interruption
241 Figure 80 โ€“ Shunt reactor voltage at current interruption
242 Table 29 โ€“ Circuit-breaker chopping numbers
243 Figure 81 โ€“ Re-ignition at recovery voltage peak for a circuit with low supply side capacitance
244 Figure 82 โ€“ Field oscillogram of switching out a 500 kV 135 Mvar solidly earthed shunt reactor
245 Figure 83 โ€“ Single-phase equivalent circuit
246 Table 30 โ€“ Chopping and re-ignition overvoltage limitation method evaluation for shunt reactor switching
249 16.3 Motor switching
250 Figure 84 โ€“ Motor switching equivalent circuit
251 Table 31 โ€“ Re-ignition overvoltage limitation method evaluation for motor switching
253 16.4 Unloaded transformer switching
254 Figure 165 โ€“ Unloaded transformer switching circuit representation
Figure 166 โ€“ Transformer side oscillation (left) and circuit-breaker transient recovery voltage (right)
256 Figure 167 โ€“ Re-ignition loop circuit
257 16.5 Shunt reactor characteristics
258 Table 32 โ€“ Typical shunt reactor electrical characteristics
259 16.6 System and station characteristics
Table 33 โ€“ Connection characteristics for shunt reactor installations
260 16.7 Current chopping level calculation
Table 34 โ€“ Capacitance values of various station equipment
261 Figure 87 โ€“ Arc characteristic
Figure 88 โ€“ Rizkโ€™s equivalent circuit for small current deviations from steady state
262 Figure 89 โ€“ Single phase equivalent circuit
263 Figure 90 โ€“ Circuit for calculation of arc instability
265 16.8 Application of laboratory test results to actual shunt reactor installations
267 Table 35 โ€“ Laboratory test parameters
268 Figure 91 โ€“ Initial voltage versus arcing time
Figure 92 โ€“ Suppression peak overvoltage versus arcing time
Figure 93 โ€“ Calculated chopped current levels versus arcing time
Figure 94 โ€“ Calculated chopping numbers versus arcing time
269 Figure 95 โ€“ Linear regression for all test points
271 Table 36 โ€“ 500 kV circuit-breaker TRVs
Table 37 โ€“ 1 000 kV circuit-breaker transient recovery voltages
Table 38 โ€“ 500 kV circuit-breaker: maximum re-ignition overvoltage values
272 16.9 Statistical equations for derivation of chopping and re-ignition overvoltages
273 17.1 General
17.2 Normal and special service conditions (refer to Clause 2 of IEC 62271-1:2007)
17.3 Ratings and other system parameters (refer to Clause 4 IEC 62271-1:2007)
274 17.4 Design and construction (refer to Clause 5 of IEC 62271-1:2007)
275 17.5 Documentation for enquiries and tenders
276 Annex A (informative) Consideration of DC time constant of the rated short-circuit current in the application of high-voltage circuit-breakers
A.1 General
A.2 Basic theory
277 Figure A.1 โ€“ Simplified single-phase circuit
278 Figure A.2 โ€“ Percentage DC component in relation to the time interval from the initiation of the short-circuit for the standard time constants and for the alternative special case time constants (from IEC 62271-100)
279 Table A.1 โ€“ X/R values
Table A.2 โ€“ Ipeak values
280 A.3 Network reduction
A.4 Special case time constants
281 A.5 Guidance for selecting a circuit-breaker
283 Table A.3 โ€“ Comparison of last major current loop parameters for the first-pole-to-clear, case 1
284 Table A.4 โ€“ Comparison of last major current loop parameters for the first-pole-to-clear, case 1: test parameters used for the reference case set at the minimum permissible values
286 Table A.5 โ€“ Comparison of last major current loop parameters of the first-pole-to-clear, case 2
287 Table A.6 โ€“ Comparison of last major current loop parameters for the first-pole-to-clear, case 2: test parameters used for the reference case set at the minimum permissible values
288 Figure A.3 โ€“ First valid operation in case of three-phase test (ฯ„ = 45 ms) on a circuit-breaker exhibiting a very short minimum arcing time
Figure A.4 โ€“ Second valid operation in case of three-phase test on a circuit-breaker exhibiting a very short minimum arcing time
289 Figure A.5 โ€“ Third valid operation in case of three-phase test on a circuit-breaker exhibiting a very short minimum arcing time
290 Table A.7 โ€“ 60 Hz comparison between the integral methodand the “I ร— t” product method
Table A.8 โ€“ 50 Hz comparison between the integral methodand the “I ร— t” product method
291 A.6 Discussion regarding equivalency
292 Figure A.6 โ€“ Plot of 60 Hz currents with indicated DC time constants
Figure A.7 โ€“ Plot of 50 Hz currents with indicated DC time constants
293 A.7 Current and TRV waveshape adjustments during tests
294 Table A.9 โ€“ Example showing the test parameters obtained during a three-phase test when the DC time constant of the test circuit is shorter than the DC time constant of the rated short-circuit current
295 Figure A.8 โ€“ Three-phase testing of a circuit-breaker with a DC time constant of the rated short-circuit breaking current longer than the test circuit time constant
296 Table A.10 โ€“ Example showing the test parameters obtained during a single-phase test when the DC time constant of the test circuit is longer than the DC time constant of the rated short-circuit current
297 Figure A.9 โ€“ Single phase testing of a circuit-breaker with a DC time constant of the rated short-circuit breaking current shorter than the test circuit time constant
298 Table A.11 โ€“ Example showing the test parameters obtained during a single-phase test when the DC time constant of the test circuit is shorter than the DC time constantof the rated short-circuit current
299 A.8 Conclusions
Figure A.10 โ€“ Single-phase testing of a circuit-breaker with a DC time constant of the rated short-circuit breaking current longer than the test circuit time constant
300 Annex B (informative) Interruption of currents with delayed zero crossings
B.1 General
B.2 Faults close to major generation
301 Figure B.1 โ€“ Single-line diagram of a power plant substation
302 Figure B.2 โ€“ Performance chart (power characteristic) of a large generator
Figure B.3 โ€“ Circuit-breaker currents i and arc voltages uarc in case of a three-phase fault following underexcited operation: non-simultaneous fault inception
303 Figure B.4 โ€“ Circuit-breaker currents i and arc voltages uarc in case of a three-phase fault following underexcited operation:Simultaneous fault inception at third phase voltage zero
Figure B.5 โ€“ Circuit-breaker currents i and arc voltages uarc in case of a three-phase fault following underexcited operation:Simultaneous fault inception at third phase voltage crest
304 Figure B.6 โ€“ Circuit-breaker currents i and arc voltages uarc under conditions of a non-simultaneous three-phase fault, underexcitedoperation and failure of a generator transformer
305 Figure B.7 โ€“ Circuit-breaker currents i and arc voltages uarc under conditions of a non-simultaneous three-phase fault following full load operation
306 Figure B.8 โ€“ Circuit-breaker currents i and arc voltages uarc under conditions of a non-simultaneous three-phase fault following no-load operation
307 Figure B.9 โ€“ Circuit-breaker currents i and arc voltages uarc under conditions of unsynchronized closing with 90ยฐ differential angle
308 Figure B.10 โ€“ Comparison of TRV test curve for out-of-phase (red) and system-source short-circuit (green)
309 Figure B.11 โ€“ Prospective (inherent) current
310 Figure B.12 โ€“ Arc voltage-current characteristic for a SF6puffer type interrupter
Figure B.13 โ€“ Assessment function e(t)
311 Figure B.14 โ€“ Network with contribution from generation and large motor load
312 Figure B.15 โ€“ Computer simulation of a three-phase simultaneous fault with contribution from generation and large motor load
313 Figure B.16 โ€“ Short-circuit at voltage zero of phase A (maximum DC component in phase A) with transition from three-phase to two-phase fault
314 Figure B.17 โ€“ Short-circuit at voltage crest of phase B (phase B totally symmetrical) and transition from three-phase to two-phase fault
315 Figure B.18 โ€“ Comparison of current zero crossing with (green) and without (blue) influence of arc voltage
316 B.3 Conditions for delayed current zeros on transmission networks
317 Figure B.19 โ€“ Recording of delayed current zero on A and B phase in the presence of a line-to-earth fault on C phase
318 Figure B.20 โ€“ Influence of arc voltage of SF6 vs. air-blast circuit-breaker
319 Figure B.21 โ€“ Earthing of the shunt reactor using a a 100 ฮฉ resistor for 200 ms insertion time
320 Annex C (informative) Parallel switching
321 Annex D (informative) Application of current limiting reactors
D.1 General
Figure D.1 โ€“ Current limiting reactor location
322 D.2 Pole factor considerations
Figure D.2 โ€“ Circuit for kpp calculation
323 D.3 Oscillatory component calculation
Figure D.3 โ€“ Variation of kpp with ratio XR/X1
Figure D.4 โ€“ Oscillatory circuit for the circuit arrangement of Figure D.1(a)
324 Figure D.5 โ€“ Oscillatory circuit for the circuit arrangement of Figure D.1(b)
325 Figure D.6 โ€“ Series reactor application case
326 Figure D.7 โ€“ TRV calculation circuit
Figure D.8 โ€“ Circuit-breaker with T30 source and varying values of CR
327 Figure D.9 โ€“ Circuit-breaker TRV with source TRV kaf = 1,4 p.u. (down from 1,54 p.u.) and t3 unchanged at 80 ยตs
Figure D.10 โ€“ Circuit-breaker TRV with source TRV kaf unchanged at 1,54 p.u. and t3 increased to 110 ยตs
328 D.4 Series reactors on shunt capacitor banks
Figure D.11 โ€“ Circuit-breaker TRV with source TRV kaf = 1,4 p.u. and t3 = 110 ยตs
329 Annex E (informative) Guidance for short-circuit and switching test procedures for metal-enclosed and dead tank circuit-breakers
E.1 General
E.2 General description of special features and possible interactions
332 Annex F (informative) Current and test-duty combination for capacitive current switching tests
F.1 General
F.2 Combination rules
333 F.3 Examples
Table F.1 โ€“ Summary of required test-duties for covering the capacitive current switching without any test-duty combination
334 Figure F.1 โ€“ Test-duty 2 combination for Case 1
Table F.2 โ€“ Case where TD2 covers LC2, CC2 and BC2
Table F.3 โ€“ Combination values for the case where TD2 covers only CC2 and BC2
335 Figure F.2 โ€“ TD1 combination for case a)
Figure F.3 โ€“ TD1 combination for case b)
Table F.4 โ€“ Combination values for case a): the combined TD1 covers CC1 and BC1
336 Figure F.4 โ€“ TD1/TD2 combination for Case 1
Table F.5 โ€“ Combination values for case b): the combined TD1 covers LC1 and CC1
Table F.6 โ€“ Combination values for a TD2 covering LC2, CC1 and BC1
337 Table F.7 โ€“ Summary of the possible test-duty combination for a 145 kV circuit-breaker, tested single-pole according to class C2
338 Table F.8 โ€“ Neutral connection prescriptions for three-phase capacitive tests
Table F.9 โ€“ Summary of required test-duties for covering the capacitive current switching without any test duty combination
339 Figure F.5 โ€“ TD2 combination for Case 2
Table F.10 โ€“ Combination values for a TD2 covering LC2, CC2 and BC2
Table F.11 โ€“ Values for the additional TD2 for covering only BC2
340 Figure F.6 โ€“ TD1 combination
Figure F.7 โ€“ TD1/TD2 combination for Case 2
Table F.12 โ€“ Values for the three a TD1 that shall be performed since no combination is possible
341 Table F.13 โ€“ Combination values for a TD2 covering LC2, CC2 and BC1
Table F.14 โ€“ Summary of the possible test-duty combination for a 36 kV circuit-breaker tested under three-phase conditions according to class C2
342 Table F.15 โ€“ Summary of required test-duties for covering the capacitive current switching without any test-duty combination
343 Figure F.8 โ€“ TD2 combination for Case 3
Figure F.9 โ€“ TD1 combination for Case 3
Table F.16 โ€“ Combination values for a TD2 covering LC2, CC2 and BC2
344 Table F.17 โ€“ Combination values for a TD1 covering LC1, CC1 and BC1
Table F.18 โ€“ Summary of the possible test-duty combination for a 245 kV circuit-breaker, tested single-phase according to class C1
345 Annex G (informative) Grading capacitors
G.1 Grading capacitors
Figure G.1 โ€“ Equivalent circuit of a grading capacitor
346 Figure G.2 โ€“ Equivalent circuit for determination of tan ฮด, power factor and quality factor
Figure G.3 โ€“ Vector diagram of capacitor impedances
349 Annex H (informative) Circuit-breakers with opening resistors
H.1 General
H.2 Background of necessity of overvoltage limitation
Figure H.1 โ€“ Typical system configuration for breaking with opening resistors
350 H.3 Basic theory on the effect of opening resistors
Figure H.2 โ€“ Circuit diagram used for the RLC method, ramp current injection
351 Figure H.3 โ€“ Relationship between TRV peak and critical damping
352 Figure H.4 โ€“ Approximation by superimposed ramp elements
354 Figure H.5 โ€“ Results of calculations done with RLC method
356 Figure H.6 โ€“ Example of a calculation of the TRV across the main interrupter for T100 using 700 ฮฉ opening resistors
357 Figure H.7 โ€“ Example of a calculation of the TRV across the main interrupter for T10 using 700 ฮฉ opening resistors
Figure H.8 โ€“ Typical TRV waveshapes in the time domain using the Laplace transform
358 H.4 Review of TRV for circuit-breakers with opening resistors for various interrupting duties
359 Figure H.9 โ€“ TRV plots for resistor interrupter for a circuit-breaker with opening resistor in the case of terminal faults
360 Figure H.10 โ€“ Typical waveforms for out-of-phase interruption โ€“Network 1 without opening resistor
361 Figure H.11 โ€“ Typical waveforms for out-of-phase interruption โ€“Network 1 with opening resistor (700 ฮฉ)
362 Figure H.12 โ€“ Typical waveforms for out-of-phase interruption โ€“Network 2 without opening resistor
363 Figure H.13 โ€“ Typical waveforms for out-of-phase interruption โ€“Network 2 with opening resistor (700 ฮฉ)
Table H.1 โ€“ Summary of TRV between main and resistor interrupters after out-of-phase interruption with/without opening resistor
364 Table H.2 โ€“ TRV on main interrupter with opening resistor for T100, T60, T30, T10, OP and SLF Ur = 1 100 kV, Isc = 50 kA, R = 700 ฮฉ
Table H.3 โ€“ TRV on resistor interrupter for T100s, T60, T30, T10, OP2 and SLF with opening resistor of 700 ฮฉ
365 Figure H.14 โ€“ Typical recovery voltage waveshape of capacitive current switching on a circuit-breaker equipped with opening resistors
366 H.5 Performance to be verified
Figure H.15 โ€“ Recovery voltage waveforms across the resistor interrupter during capacitive current switching by a circuit-breaker with opening resistors
367 Figure H.16 โ€“ Timing sequence of a circuit-breaker with opening resistor
368 Figure H.17 โ€“ Voltage waveshapes for line-charging current breaking operations
369 H.6 Time sequence of main and resistor interrupters
370 H.7 Current carrying performance
H.8 Dielectric performance during breaking tests
H.9 Characteristics of opening resistors
371 Table H.4 โ€“ Example of calculated values on main and resistor interrupter
372 Annex I (informative) Circuit-breaker history
373 Figure I.1 โ€“ Manufacturing timelines of different circuit-breaker types
BSI PD IEC/TR 62271-306:2012+A1:2018
$215.11