IEEE 367 1988
$86.67
IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault
Published By | Publication Date | Number of Pages |
IEEE | 1988 | 166 |
Revision Standard – Inactive – Superseded. Superseded by IEEE Std 367-1996. Guidance is provided for the calculation of interfering voltages and their appropriate reduction from worst-case values for use in wire-line telecommunication protection design. Information is also included for the determination of the fault current and earth-return current levels; their probability, waveform, and duration; and the impedance to remote earthing points used in these ground potential rise (GPR) and longitudinally induced voltage calculations. The zone of influence of the power station GPR; the calculation of the inducing currents; the mutual impedance between power and wire-line telecommunication facilities and shield factors; and the channel time requirements for wire-line telecommunication facilities where noninterruptible channels are required for protective relaying and other purposes are covered.
PDF Catalog
PDF Pages | PDF Title |
---|---|
10 | Example 2: Nonuniform Exposure Mutual Reactance of Ground-Return Circuits in SI Units |
14 | 1 Scope |
16 | 2 Introduction Wire-Line Telecommunication Circuits Faults on Power Systems |
17 | Power Station Ground Impedance to Remote Earth |
19 | Establishing Net Fault Current Values Division of Fault Current |
20 | Calculating the Inducing Current Ground Potential Rise (GPR) Telecommunication Utilities |
21 | Transient Voltages Resulting from Power System Operation Utilities |
22 | Defined in ANSI/IEEE Std 487-1980 [51 Summary of Introduction |
24 | 3 Definitions |
26 | 4 References |
28 | 5 Electric Power Station Ground Potential Rise (GPR) 5.1 Statement of the Problem Determination of Appropriate Symmetrical GPR |
30 | GroundSource |
33 | L-G and Three-phase Fault Simulation |
35 | Circuit for Total Zero-Sequence Current (31AOT) Reduction Power Line Shielding |
36 | Circuit for L-G and Three-phase Fault Analysis |
39 | Complete Faulted Circuit |
41 | Fig |
42 | R-O-W 1 Conductor Configuration Fig |
43 | 230kVBusFault 44 kV Bus Fault Fig |
46 | Protection |
47 | 230 kV Bus Fault Fig |
48 | Fig |
49 | A Sample Computer Program Output Fig |
50 | Left Station Potential Versus Tower Numbers Fig |
51 | Fig |
52 | 5.4 Extraordinary Possibilities Fig |
53 | Example of GPR Calculations and Volt Time Area Calculation Fig |
58 | Current Curve and Determination of Area No 1 Current Curve and Determination of Area No 2 Current Curve and Determination of Area No 3 |
60 | Graphical Representations of Peak Currents |
63 | Current B Current BCurrent Determination of Area No 3 for Initial Phase B Current Determination of Area No 4 for Initial Phase B Current Current Current |
65 | 5.6 Summary Area No Total Current for an Evolving Fault |
66 | Combined Relative Wave Forms |
68 | Conditions 6.1 Statement of the Problem 6.2 Introduction |
69 | 6.3 General |
70 | General Configuration for Mutual Impedance |
72 | Example 1: Uniform Exposure |
73 | Illustration for Example |
75 | Evaluation of Mutual Impedance Mutual Resistance of Ground-Return Circuits |
76 | Mutual Reactance of Ground-Return Circuits |
77 | Mutual Impedance of Ground-Return Circuits |
78 | Calculation of Mutual Impedance (Per Unit Length) Mutual Resistance of Ground-Return Circuits in SI Units |
80 | Mutual Impedance of Ground-Return Circuits in SI Units |
81 | Inductive Exposure for Example Earth Resistivity |
82 | Converging Inductive Exposure Diverging Inductive Exposure |
83 | Curves Correction for Difference in Line Heights |
84 | Example of Calculations for Part |
85 | Table 3 Example of Calculations for Part I1 |
86 | Electric Supply Line with Double-End Feed Fault Location for Maximum Induced Voltage and2 |
87 | Correction Factors for Difference in Line Heights Fig |
88 | Shield Factor for Example |
91 | Shield Factors for Supply Line with Overhead Ground Wires |
92 | Table 5 Shield Factors for Alpeth Communications Cable Table 6 Shield Factors for Stalpeth Communications Cable Shield Factors for Tape Armored Communications Cable |
93 | Typical Supply Line Fault Current Distribution Telecommunication Cable with Continuous Leakage |
94 | Faults |
95 | Example |
100 | with a Longitudinally Induced Voltage 7.1 Statement of Problem 7.2 General |
101 | Illustrations for Examples 1 and Fig |
102 | 7.3 Example 1: Symmetrical Fault Current |
103 | 7.4 Example 2: Asymmetrical Fault Current |
106 | 8 Power System Fault Current Probability 8.1 General 8.2 Probability Analysis |
108 | 9 Zone of Influence of Ground Potential Rise (GPR) 9.1 Conductive Interference 9.2 Equipotential Lines |
109 | Zone of Influence of GPR and its Distribution Fig |
111 | Boundary of the GPR Zone of Influence Fig |
112 | 9.3 Potential Contour Surveys |
113 | The DC Transient Component |
114 | The Effects of GPR Within the Zone of Influence The Transfer of a GPR Electric Power Station or Transmission Line Tower |
115 | Influence and Subject to a GPR Interference |
116 | Embedded in the Soil Caused by a Tower Ground Grid |
117 | Ring Electrode |
118 | Telecommunication Cable as Influenced Conductor |
119 | Influence and Subject to Interference Cable Subject to Interference) |
120 | Earth Electrode |
122 | Fig 48) at 1000 V Interfering Earth Electrode Voltage |
123 | Influence and Subject to Interference Determination of the Boundary of the Zone of Influence |
125 | Power Stations |
128 | 9.12 Safety Considerations |
130 | Induced Voltages or Both 10.1 Introduction 10.2 Mitigating Factors Applicable to Fault Current Calculation |
131 | 10.3 Mitigating Factors Applicable to GPR Calculations |
132 | the Calculated GPR 10.5 Chemical Grounds |
134 | 11 Communications Channel Time Requirements 11.1 Introduction 11.2 Power Systems |
135 | 11.3 Protection Relays |
136 | 11.4 Relaying Schemes Typical Three-Zone Impedance Relay Reach Fig |
137 | Typical Impedance Protection System with Communications Fig |
139 | Fig Simplified Transfer Trip System |
140 | 11.5 Summary Table 8 Typical Trip and Reclose Sequence |
142 | 12 Administrative Guidelines |
146 | 13 Bibliography |
152 | Mutual Impedance Calculations A1 General A2 Calculation of Mutual Impedance A3 Mutual Impedance Program-HP-67/97 |
153 | Fig A1 Configuration for Mutual Impedance-Example Fig A2 Configuration for Mutual Impedance-Example 2(a) Fig A3 Configuration for Mutual Impedance-Examples 2(b 2(c) |
157 | Fig A4 User Instructions |
158 | Table A1 External Mutual Impedance Program-HP-67/97 |
160 | INDEX |