{"id":78315,"date":"2024-10-17T18:18:55","date_gmt":"2024-10-17T18:18:55","guid":{"rendered":"https:\/\/pdfstandards.shop\/product\/uncategorized\/md-cityofgaithersburg-3-n-a\/"},"modified":"2024-10-24T19:36:37","modified_gmt":"2024-10-24T19:36:37","slug":"md-cityofgaithersburg-3-n-a","status":"publish","type":"product","link":"https:\/\/pdfstandards.shop\/product\/publishers\/md\/md-cityofgaithersburg-3-n-a\/","title":{"rendered":"MD CityofGaithersburg 3 N\/A"},"content":{"rendered":"

0<\/p>\n

PDF Catalog<\/h4>\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n
PDF Pages<\/th>\nPDF Title<\/th>\n<\/tr>\n
9<\/td>\nNFPA 1, S1.8, 1.9S, 1.10, and 1.11.3. Delete.
NFPA 1, 1.12.S20S.U7.U Change the word \u201cshall\u201d\u009d to \u201cmay\u201d\u009d.
NFPA 1, 2.2. Delete the referenced publication NFPA 5000, Building Construction and Safety Code, S2006S U2009U edition. Wherever NFPA 5000 is referenced, other than for extracted text, substitute the \u201cCity of Gaithersburg Building Code\u201d\u009d.
UNFPA 1, 3.3.115. Add \u201cand as referenced in Public Safety Article, \u00a710-101, Annotated Code of Maryland\u201d\u009d.
S(4)S U(5)U NFPA 1, 3.3.S165S U170U.6. Delete the phrase \u201cmore than 3 but\u201d\u009d.
S(5)S U(6)U NFPA 1, 3.3.S165S U170U.7 and 6.1.4.1. Delete the phrase \u201cfour or more\u201d\u009d.
S(6)S U(7)U NFPA 1, 3.3.S165.19S U170.20U. Replace the word \u201cthree\u201d\u009d with \u201cfive\u201d\u009d and delete the phrase \u201c, if any, accommodated in rented rooms\u201d\u009d.
S(7)S U(8)U NFPA 1, 3.3.S165.22S U170.23U and 6.1.9.1. Replace the word \u201cfour\u201d\u009d with \u201csix\u201d\u009d.
U(9) NFPA 1, 4.5.8.1 and 10.4.1. Delete the phrase \u201cfor compliance with the provisions of this Code\u201d\u009d.
U(10) NFPA 1, 4.5.8.3 and 10.4.3. Delete the phrase \u201cby the Code\u201d\u009d. <\/td>\n<\/tr>\n
10<\/td>\nS(8 SU11)U NFPA 1, 10.1.2. Add \u201cexcept as amended by COMAR 29.06.01.07, COMAR 29.06.01.08U,and COMAR 29.06.01.09U and the City of Gaithersburg Fire Code.\u201d\u009d
U(12) NFPA 1, 10.5.1. After the phrase \u201cby the AHJ\u201d\u009d, insert \u201cor incident commander\u201d\u009d.
U(13) NFPA 1, 10.11.6. Delete the text and replace with the following:
U\u201cThe use of charcoal burning, other fuel burning, or electric cooking equipment outside of any multi-family dwelling shall be prohibited unless such cooking equipment is at least twenty (20) feet from every part of the building. The provisions of th…
U(14) NFPA 1, 10.11.6.1. Delete.
U(15) NFPA 1, 10.12.1.1.1. Add new subsection 10.12.1.1.1 to read as follows:
U\u201c10.12.1.1.1 Subject to the approval of the AHJ, individual suites within structures and rear store entrances and\/or access from service corridors shall be clearly identified.
U(16) NFPA 1, 10.12.1.2 and 10.12.1.3. After the phrase \u201cAddress numbers\u201d\u009d insert \u201cor premises identification\u201d\u009d.
U(17) NFPA 1, 10.12.1.4 Add new subsection 10.12.1.4 to read as follows:
U\u201c10.12.1.4 Where required by the AHJ, symbols in compliance with NFPA 170, Standard for Fire Safety and Emergency Symbols, shall be used.
S(9SU18)U NFPA 1, 10.14.1, Table 10.14.1U.1U and 10.14.9. Delete the text and replace with the following:
\u201c10.14.1 Combustible vegetation, including natural cut Christmas trees shall be in accordance with COMAR 29.06.S06S U01U and the City of Gaithersburg Fire Code.\u201d\u009d
U(19) NFPA 1, 10. 16.1. Delete all text after the word \u201cwithin\u201d\u009d and replace with \u201c15 feet of a property line, building, or adjacent pile of combustible material.\u201d\u009d <\/td>\n<\/tr>\n
11<\/td>\nU(20) NFPA 1, 10.16.3. Add the following: \u201cThe AHJ shall have the authority to increase the separation distance where it is determined by the AHJ that a higher hazard to the adjoining property exists.\u201d\u009d
U(21) NFPA 1, 10.16.5. Add \u201cand 10, 000 square feet in area.\u201d\u009d
U(22) NFPA 1, 10.16.6. Add new subsection 10.16.6 to read as follows:
U\u201c10.16.6 The AHJ shall have the authority to require that outdoor storage of any combustible material be enclosed by an approved fence or other protective enclosure to prevent unauthorized access.\u201d\u009d
U(23) NFPA 1, 11.1.11 Add new subsection 11.1.11 to read as follows:
S(10SU24)U NFPA 1, 11.1.S7.3S U9.3.3U. Add new subsection 11.1.S 7.3S U9.3.3U to read as follows:
\u201c11.1.S 7.3S U9.3.3U Doors Sleading intoS UtoU electrical control panel rooms shall be marked with a Uplainly visible andU legible sign stating \u2018ELECTRICUALU ROOM\u2019 or similar approved wording Uin contrasting letters not less than 1.5 inches high and n…
U(25) NFPA 1, 11.9.1 Delete the phrase \u201cthe fire department\u201d\u009d and replace with \u201cMontgomery Count Fire & Rescue Service\u201d\u009d.
S(11SU26)U NFPA 1, 13.2.2.2. Delete the text and replace with the following:
\u201c13.2.2.2 New buildings shall have standpipe systems installed where required by the City of Gaithersburg Building Code or the City of Gaithersburg Fire Code.\u201d\u009d <\/td>\n<\/tr>\n
12<\/td>\nU(27) NFPA 1, 13.3.1.2.1. Add new subsection 13.3.1.2.1 to read as follows:
U\u201c13.3.1.2.1 Drop-out ceilings as referenced in NFPA 13 are prohibited in new ceiling installations.\u201d\u009d
S(12) NFPA 1, 13.3.2.24.2. Add the following exception:
U(28) NFPA 1, 13.3.3.1 and 13.3.3.2. Delete the phrase \u201cA sprinkler system installed in accordance with this Code\u201d\u009d and replace with \u201cSprinkler systems\u201d\u009d.
U(29) NFPA 1, 13.4.1.1.1. Add new subsection 13.4.2.1.1.1 to read as follows:
U\u201c13.4.1.1.1 No fire pump component, including the pump, driver, or controller, shall be permitted to be installed in below-ground vaults or pits unless approved by the AHJ.\u201d\u009d
U(30) NFPA 1, 13.6.2. Add \u201cunless otherwise permitted by the AHJ.\u201d\u009d
U(31) NFPA 1, 13.7.2.22.1.2 and 13.7.2.22.1.3. After the phrase \u201cStorage occupancies\u201d\u009d, insert \u201cless than three stories\u201d\u009d.
S(13SU32) UNFPA 1, 18.1.1.1 and 18.1.1.2. Replace the phrase \u201cfire department\u201d\u009d with \u201cCity of Gaithersburg\u201d\u009d.
S(14SU33) UNFPA 1, 18.2.2.1. Delete the text and replace with the following: <\/td>\n<\/tr>\n
13<\/td>\nS(15) NFPA 1, 18.2.3.1.3. Amend to read \u201cThe requirements of 18.2.3.1 through 18.2.3.2.1 shall be permitted to be modified by the AHJ.\u201d\u009d
U(34)U UNFPA 1, 18.2.3.2.1. After the phrase \u201cexterior door\u201d\u009d insert \u201cacceptable to the AHJ\u201d\u009d and after the phrase \u201cprovides access to\u201d\u009d insert \u201call floors of\u201d\u009d.
S(16SU35)U NFPA 1, 20.3.S3.1.1S U4.1.1U. Delete the phrase \u201cmore than 3 but\u201d\u009d.
S(17SU36)U NFPA 1, 20.3.S3.2.3.4.1S U4.2.3.5.1U. Add the following exception:
\u201cException: Day-care homes.\u201d\u009d
S(18SU37)U NFPA 1, 20.3.S3.2.3.4.5S U4.2.3.5.4U Add the following exception:
\u201cException: Day-care homes with not more than three clients for overnight lodging.\u201d\u009d
S(19SU38) UNFPA 1, 25.2.2.1. Add \u201cor other approved testing standard approved by the State Fire Marshal.\u201d\u009d
S(20SU39)U NFPA 1, 42.S2.S7.5.1. Add a second sentence to read as follows: \u201cSuch facilities shall comply with the State of Maryland Fire Prevention Code (COMAR 29.06.01)\u201d\u009d.
S(21SU40)U NFPA 1, 50.2.1.10. Add new subsection 50.2.1.10 to read as follows:
\u201c50.2.1.10 Commercial outdoor cooking operations shall comply with the State of Maryland Fire Prevention Code (COMAR 29.06.01).\u201d\u009d
S(22SU41)U NFPA 1, 65.1. Add the following: \u201cExplosives, Fireworks and Model Rocketry shall comply with this chapter and with the State of Maryland Fire Prevention Code (COMAR 29.06.01).\u201d\u009d <\/td>\n<\/tr>\n
14<\/td>\nSNFPA 30A, 7.3.6.1 and 7.3.6.3. Add the following exception:
S(2S1) NFPA 80, S1-10.1S U4.7.1U. Add the following: \u201cRelease of fire doors and shutters shall not be solely by fusible link, and shall be activated by one or more of the following methods:
S(3SU2)U NFPA 96, 1.1.1. Add the following exception:
S(4SU3)U NFPA 101, General. Delete all references to NFPA 5000, Building Construction and Safety Code, and substitute \u201cthe City of Gaithersburg Building Code.\u201d\u009d
S(5SU4)U NFPA 101, 1.4.4. Add new subsection 1.4.4 to read as follows: <\/td>\n<\/tr>\n
15<\/td>\nS(6SU5)U NFPA 101, 3.3.S52S U57U.3. Add new subsection 3.3.S52S U57U.3 to read as follows:
U(6) NFPA 101, 3.3.115. In the second sentence, replace \u201c6 ft (1830mm)\u201d\u009d with \u201c20 ft (6096 mm)\u201d\u009d (both instances).
U(7)U UNFPA 101, 3.3.250. Replace the phrase \u201clevel of exit discharge\u201d\u009d with \u201cfirst story above grade plane\u201d\u009d.
S(7SU8)U NFPA 101, 3.3.S122S U131U.1. Delete the phrase \u201cmore than three, but\u201d\u009d.
S(8SU9)U NFPA 101, 3.3.S168S U178U.4. Delete the phrase \u201cfour or more\u201d\u009d.
S(9SU10)U NFPA 101, 3.3.S168S U178U.12. After the phrase \u201cor portion thereof\u201d\u009d insert \u201cthat does not qualify as one- and two-family dwelling\u201d\u009d, Uand replace the word \u201cfour\u201d\u009d with \u201csix\u201d\u009dU.
U(11) NFPA 101, 4.5.8 and 4.6.13.1. Delete the phrase \u201cfor compliance with the provisions of this Code\u201d\u009d.
U(12) NFPA 101, 4.6.13.3. Delete the phrase \u201cby the Code\u201d\u009d.
S(10SU13)U NFPA 101, 4.8.2.4. Add new subsection 4.8.2.4 to read as follows:
S(11SU14)U NFPA 101, 6.1.4.1. Delete the phrase \u201cfour or more\u201d\u009d. <\/td>\n<\/tr>\n
16<\/td>\nS(12SU15)U NFPA 101, 6.1.9.1. After the phrase \u201cor portion thereof\u201d\u009d insert \u201cthat does not qualify as one- and two-family dwelling\u201d\u009d.
U(16) NFPA 101, 7.2.1.2.2.2(5). Add new subsection 7.2.1.2.2.2(5) to read as follows:
U\u201c(5) For power operated sliding door assemblies that utilize a fixed panel adjacent to and on the exterior of the sliding panel, and the door system is designed such that the fixed panel also breaks away to become side hinged in the emergency breakou…
U(17) NFPA 101, 7.2.1.6.3. After the phrase \u201cWhere permitted\u201d\u009d, insert \u201cby the AJH and\u201d\u009d.
S(13SU18)U NFPA 101, 7.2.3.9.2(3)(b). Delete.
S(14SU19)U NFPA 101, Table 7.3.1.2. Under \u201cBusiness Use\u201d\u009d add \u201cNew Business Occupancy shell space shall be calculated at 65 ft\u00b2 (6.0 m\u00b2) per person.\u201d\u009d
S(15) NFPA 101, 7.5.1.3.1.1. Add new subsection 7.5.1.3.1.1 to read:
S(16SU20)U NFPA 101, 7.9.1.2. In the first sentence, replace the word \u201conly\u201d\u009d with the phrase \u201cbut not limited to\u201d\u009d.
S(17SU21)U NFPA 101, 7.10.8.3.2. Add the following: \u201cWhen located at a door, the sign shall be visible with the door in any position, or if the sign is located on the door, the door shall be self-closing.\u201d\u009d <\/td>\n<\/tr>\n
17<\/td>\nS(18SU22)U NFPA 101, 7.12.1(4). Add item (4) to read as follows:
S(19SU23) UNFPA 101, 8.6.6(3). Add the following: \u201cBuildings wherein the communicating space(s) is (are) provided with automatic smoke detection and alarm in accordance with NFPA 72 will be considered to satisfy the requirements of \u2018readily obvious\u2019.\u201d\u009d
S(20SU24)U NFPA 101, 8.6.7(6)(b). Delete all text after the word \u201care\u201d\u009d and replace with \u201clocated at the annunciator panel or in the Fire Control Room.\u201d\u009d
S(21SU25)U NFPA 101, 9.1.5. Add new subsection 9.1.5 to read as follows:
S(22SU26) UNFPA 101, 9.6.1.6. Add the following: \u201cWhen a property owner or the owner\u2019s agent cannot be contacted to establish a fire watch, the MCDFRS at their discretion may provide the fire watch and charge the property owner the inspection overtim…
U(27) NFPA 101, 9.6.2.6. Add the following: \u201cThis paragraph does not permit the omission of manual fire alarm boxes in accordance with other provisions of this subsection unless specifically permitted by Chapters 11 through 43.\u201d\u009d <\/td>\n<\/tr>\n
18<\/td>\nS(23) NFPA 101, 9.6.2.9.2. At the end of the sentence, add the phrase \u201cand have secondary battery back-up power\u201d\u009d.
U(28) NFPA 101, 9.6.2.10.1.2. Delete all text after the word \u201crequired\u201d\u009d.
U(29) NFPA 101, 9.6.2.10.2. Delete the word \u201cexisting\u201d\u009d and delete all text after the word \u201cpowered\u201d\u009d and replace with \u201cby the building electrical system and have battery back-up power\u201d\u009d.
S(24SU30) UNFPA 101, 9.6.2.S11.S U12.U Add new subsection 9.6.2.S11.S U12.U to read as follows:
S(25SU31) UNFPA 101, 9.6.3.2.1. Delete the word \u201clobby,\u201d\u009d.
S(26SU32) UNFPA 101, 9.6.3.3. Delete all text after the word \u201cdelay\u201d\u009d and replace with \u201cto a listed central station in accordance with 9.6.4.\u201d\u009d
S(27SU33)U NFPA 101, 9.6.3.4. At the end of the sentence, add the phrase \u201cand only when the initial fire alarm signal is automatically transmitted without delay to a listed central station in accordance with 9.6.4.\u201d\u009d
S(28SU34) UNFPA 101, 9.6.3.9. Add the following: \u201cNew systems having voice notification shall be by automatic, pre-recorded announcement in accordance with Section 9.6. Live voice as the sole means of notification method is prohibited.\u201d\u009d
S(29SU35) UNFPA 101, 9.6.4.2. Delete all text after the word \u201cautomatically\u201d\u009d and replace with \u201cto a listed central station.\u201d\u009d
S(30SU36) UNFPA 101, 9.6.4.3. Delete.
S(31SU37) UNFPA 101, 9.6.5.2(3). Add the following exception: <\/td>\n<\/tr>\n
19<\/td>\n\u201cException to (3): Manual fire alarm initiation shall not activate floor- or zone-dependent smoke control systems.\u201d\u009d
S(32SU38) UNFPA 101, 9.7.1.1.1. Add new subsection 9.7.1.1.1 to read as follows:
\u201c9.7.1.1.1 For new ceiling installations, drop-out ceilings as referenced in NFPA 13, Subsection 8.14.13 shall be prohibited.\u201d\u009d
S(33SU39)U NFPA 101, 9.7.1.2. Delete the second sentence and replace with the following: \u201cThe sprinkler piping shall be valved with the domestic water system. Any and all work shall be performed only by a licensed sprinkler contractor.\u201d\u009d
S(34SU40)U NFPA 101, 9.7.2.2. Delete all text and replace with the following: \u201cWhere a supervised automatic sprinkler system is required by another section of this Code, waterflow alarms must be automatically transmitted to a listed central station.\u201d\u009d
S(35SU41) UNFPA 101, 9.7.3.1. Delete all text and replace with the following: \u201cWhere water as an extinguishing agent is not compatible with the fire hazard or is prohibited by law, statute or ordinance, the affected area shall be equipped with an app…
U(42)U UNFPA 101, 9.7.5. Delete the phrase \u201crequired by this Code\u201d\u009d.
S(36SU43) UNFPA 101, 9.7.6.1. Add the following: \u201cWhen a property owner or the owner\u2019s agent cannot be contacted to establish a fire watch, the MCDFRS at their discretion may provide the fire watch and charge the property owner the inspection overtim…
S(37SU44) UNFPA 101, 11.8.3.1.1. Add new subsection 11.8.3.1.1 to read as follows: <\/td>\n<\/tr>\n
20<\/td>\nS(38SU45) UNFPA 101, 11.8.5(6). Add the following: \u201cand remote starting\u201d\u009d.
S(39SU46) UNFPA 101, 11.8.5(8). Add the following: \u201cand remote starting only.\u201d\u009d
S(40SU47) UNFPA 101, 11.11.2.1. Add the following: \u201cor other approved testing standard approved by the State Fire Marshal.\u201d\u009d
S(41SU48) UNFPA 101, 12.2.2.2.4. Delete.
U(49) NFPA 101, 12.4.7.1. Add the following: \u201cIndoor children\u2019s playground structures shall comply with this section and section 10.20 of the 2009 Edition of NFPA 1.\u201d\u009d
S(42SU50) UNFPA 101, 12.7.7.3.1 and 13.7.7.3.1. Add new subsections 12.7.7.3.1 and 13.7.7.3.1 to read as follows: <\/td>\n<\/tr>\n
21<\/td>\nS(43SU51) UNFPA 101, 14.2.11.1.1(1). After the word \u201ctools\u201d\u009d, insert the phrase \u201ckeys, special knowledge, or excessive force\u201d\u009d.
S(44SU52) UNFPA 101, 16.1.1.6 and 17.1.1.6. Add new subsections 16.1.1.6 and 17.1.1.6 to read as follows:
S(45SU53)U NFPA 101, 16.2.11.1.1(3) & 17.2.11.1.1(3). Add the following exception:
S(46SU54) UNFPA 101, 16.3.4.5(1) and 17.3.4.5(1). Add the following exception: <\/td>\n<\/tr>\n
22<\/td>\nS(47SU55) UNFPA 101, 16.3.5.4. Add new subsection 16.3.5.4 to read as follows:
S(48SU56) UNFPA 101, 16.6.1.1.2 and 17.6.1.1.2. Delete the phrase \u201cmore than three, but\u201d\u009d.
S(49SU57) UNFPA 101, 16.6.1.4.1.1 and 17.6.1.4.1.1. Delete the phrase \u201cmore than three, but\u201d\u009d, change \u201cseven\u201d\u009d to \u201cnine\u201d\u009d and after the existing text add \u201cWhere 3 or more clients, and up to a maximum of 4 clients incapable of self-preservation are being…
S(50SU58) UNFPA 101, 16.6.1.4.1.2 and 17.6.1.4.1.2. Change \u201c7\u201d\u009d to \u201c9\u201d\u009d.
S(51SU59) UNFPA 101, 16.6.1.7.1 and 17.6.1.7.1, delete existing wording and replace with the following:
\u201cIn family day-care homes, a day-care provider’s own children Sunder the age of two yearsS Uincapable of self-preservationU shall be counted as clients served and the following shall apply:
At any given time, a day-care provider may not care for more than eight clients, of whom no more than four may be Sunder the age of two yearsS Uincapable of self-preservationU; and
An adult to child ratio of at least one adult to every two children Sunder the age of two yearsS Uincapable of self-preservationU shall be maintained at all times.\u201d\u009d
UIf approved by the City of Gaithersburg Fire Marshal, the staff-to-client ratio may be modified where safeguards are provided in addition to those specified by local codes and ordinances.
S(52SU60)U NFPA 101, 16.6.2.1 and 17.6.2.1. Add the following: \u201cBulkhead doors shall not be permitted to serve as primary means of escape.\u201d\u009d
S(53SU61) UNFPA 101, 16.6.2.2 S(Reserved)S and 17.6.2.2 S(Reserved). InsertS UDelete the word \u201cReserved\u201d\u009d, and replace withU the following: <\/td>\n<\/tr>\n
23<\/td>\nS(54SU62) UNFPA 101, 16.6.2.3 S(Reserved)S and 17.6.2.3 S(Reserved). InsertS UDelete the word \u201cReserved\u201d\u009d, and replace withU the following:
S(55SU63) UNFPA 101, 16.7.1.1 and 17.7.1.1. Add new subsections 16.7.1.1 and 17.7.1.1 to read as follows: <\/td>\n<\/tr>\n
24<\/td>\nS(56SU64) UNFPA 101, 16.7.4.1 and 17.7.4.1. Add the following exception:
S(57SU65) UNFPA 101, 16.7.5 and 17.7.5. Add the following exception:
S(58SU66) UNFPA 101, 20.3.5.1. Renumber the existing sections 20.3.5.1 through 20.3.5.3 to 20.3.5.2 through 20.3.5.4 respectively, and add a new subsection 20.3.5.1 to read as follows: \u201cBuildings containing new ambulatory health care occupancies loca…
U(67) NFPA 101, 22.4.5.1.3. Delete the phrase \u201cor 22.4.5.1.5\u201d\u009d.
U(68) NFPA 101, 22.4.5.1.4(1) and 22.4.5.1.4(2). Change \u201c2\u201d\u009d to \u201c\u00bd\u201d\u009d.
U(69) NFPA 101, 22.4.5.1.5 and 22.4.5.2. Delete.
U(70) NFPA 101, 23.4.5.1.3. Delete the phrase \u201cor 23.4.5.1.5\u201d\u009d
U(71) NFPA 101, 23.4.5.1.4(1) and 23.4.5.1.4(2). Change \u201c2\u201d\u009d to \u201c\u00bd\u201d\u009d.
U(72) NFPA 101, 23.4.5.1.5 and 23.4.5.2. Delete.
S(59SU73) UNFPA 101, 24.1.1.1. Place a period after the word “dwellings” and replace the remainder of the sentence with the following: <\/td>\n<\/tr>\n
25<\/td>\nS(60SU74) UNFPA 101, 24.2.2.3.3. After the phrase \u201c5.7 ft\u00b2 (0.53 m\u00b2)\u201d\u009d insert the phrase \u201cor not less than 5.0 ft\u00b2 when at grade\u201d\u009d.
S(61) NFPA 101, 24.2.5.1. Add the following exception:
S(62) NFPA 101, 24.3.4.1(1). Delete all text after the word \u201crooms\u201d\u009d
S(63SU75) UNFPA 101, 24.3.4.4 and 26.3.4.S6S 7 . Add new subsections U24.3.4.4 and 26.3.4.7U to read as follows: \u201cUCarbon Monoxide Alarms.U In new construction, carbon monoxide alarms shall be installed in accordance 9.6.2.S11S U12U.\u201d\u009d
U(76) NFPA 101, 26.1.1.1. After the word \u201cbuildings\u201d\u009d insert the phrase \u201cthat do not qualify as one- and two-family dwellings, and\u201d\u009d. <\/td>\n<\/tr>\n
26<\/td>\nU(77) NFPA 101, 26.3.4.5.3. Delete.
S(64SU78) UNFPA 101, 28.3.4.3.5. Delete all text after the word \u201cprovided\u201d\u009d.
S(65SU79) UNFPA 101, 28.3.4.S6S 7. Add new subsection 28.3.4.S 6S 7 to read as follows:
S(66SU80) UNFPA 101, 29.3.4.5.2, 30.3.4.3.3, and 30.3.4.3.4. Delete.
S(67SU81) UNFPA 101, 30.3.4.S6S 7. Add new subsection 30.3.4.S6S 7 to read as follows:
\u201c30.3.4.S 6S U7 Carbon Monoxide Alarms.U Carbon monoxide alarms shall be installed in accordance 9.6.2.S 11S U12U.\u201d\u009d
S(68) NFPA 101, 31.3.4.5.1. Before the word \u201coutside\u201d\u009d, insert the phrase \u201cinside each sleeping area,\u201d\u009d.
S(69SU82) UNFPA 101, 31.3.4.5.2. UDelete.U SAt the end of the sentence, add the phrase \u201conly in sleeping rooms that were not required to have smoke alarms powered by the building electrical system when the building was constructed.\u201d\u009d
U(83) NFPA 101, 31.3.4.5.3. Delete the phrase \u201cor a complete, supervised automatic sprinkler system in accordance with 31.3.5\u201d\u009d.
U(84) NFPA 101, 31.3.4.5.4. After the word \u201cpowered\u201d\u009d, insert the phrase \u201cunless another state or local fire prevention code or building code or similar governmental code requires smoke alarms to be powered by the building electrical service\u201d\u009d.
S(70SU85) UNFPA 101, 32.2.2.3.1(3)S and 33.2.2.3.1(3)S. After the phrase \u201c5.7 ft\u00b2 (0.53 m\u00b2)\u201d\u009d insert the phrase \u201cor not less than 5.0 ft\u00b2 when at grade\u201d\u009d.
S(71SU86) UNFPA 101, S32.2.3.4.4S U32.2.3.4.5U. Add new subsection S32.2.3.4.4S U32.2.3.4.5U to read as follows:
\u201cS32.2.3.4.4S U32.2.3.4.5 Carbon Monoxide Alarms.U Carbon monoxide alarms shall be installed in accordance 9.6.2.S 11S U12U.\u201d\u009d <\/td>\n<\/tr>\n
27<\/td>\nS(72) NFPA 101, 32.3.1.3. Delete all text after the word \u201cwith\u201d\u009d and replace with \u201cSection 33.3.1.3 and the City of Gaithersburg Building Code.\u201d\u009d
S(73SU87) UNFPA 101, 32.3.3.4.S9S U10U . Add new subsection 32.3.3.4.S 9S U10U to read as follows:
U(88) NFPA 101, 32.7.5.2.2 and 32.7.5.3.2. Delete all text after the word \u201ctested\u201d\u009d.
U(89) NFPA 101, 33.2.2.3.1(3). After the phrase \u201c5.7 ft\u00b2 (0.53 m\u00b2)\u201d\u009d insert the phrase \u201cor not less than 5.0 ft\u00b2 when at grade\u201d\u009d.
U(90) NFPA 101, 33.2.3.4.3.1. Delete the phrase \u201c33.2.3.4.3.6 and\u201d\u009d.
U(91) NFPA 101, 33.2.3.4.3.3. After the word \u201cfor\u201d\u009d, insert the phrase \u201csleeping rooms,\u201d\u009d.
S(74SU92)U NFPA 101, 33.2.3.4.3.5 Sand 33.3.3.4.7.1S. After the word \u201csystem\u201d\u009d, insert the phrase \u201cand have secondary battery backup\u201d\u009d Uand add the following exception:
U\u201cException: Unless another state or local fire prevention code or building code or similar governmental code requires smoke alarms to be powered by the building electrical service, smoke alarms installed in sleeping rooms in order in order to comply …
U(93) NFPA 101, 33.2.3.4.3.6. Delete.
U(94) NFPA 101, 33.3.3.4.7.1. After the word \u201csystem\u201d\u009d, insert the phrase \u201cand have secondary battery backup\u201d\u009d and add the following exception:
U\u201cException: Unless another state or local fire prevention code or building code or similar governmental code requires smoke alarms to be powered by the building electrical service, smoke alarms installed in sleeping rooms in order in order to comply …
U(95) NFPA 101, 33.3.3.4.7.2 and 33.3.3.4.7.3. Delete. <\/td>\n<\/tr>\n
28<\/td>\nU(96) NFPA 101, 33.7.5.2.2 and 33.7.5.3.2. Delete all text after the word \u201ctested\u201d\u009d.
S(75SU97) UNFPA 101, 36.1.2.3 Sand 37.1.2.3S. Add new subsectionSs S36.1.2.3 Sand 37.1.2.3S to read as follows:
U(98) NFPA 101, 36.2.5.11(4). Add the following: The egress path shall be defined by a fixed barrier or guardrail with a height of at least 42 inches and at least one intermediate rail. Openings in the fixed barrier or guardrail for passage shall be…
S(76SU99) UNFPA 101, 36.3.4.1 Sand 37.3.4.1S. After the word \u201coccupancies\u201d\u009d, insert the phrase \u201cand multiple story Class B mercantile occupancies\u201d\u009d.
S(77SU100)UNFPA 101, 36.4.4.4.3.1(3). Delete.
U(101) NFPA 101, 36.4.4.4.3.2. At the end of the sentence, add the phrase \u201cas permitted in 9.6.3.5.7.\u201d\u009d
U(102) NFPA 101, 36.4.4.8(1)(b). Delete.
U(103) NFPA 101, 37.1.2.3. Add new subsection 37.1.2.3 to read as follows:
U(104) NFPA 101, 37.2.5.11(4). After the word \u201cdefined\u201d\u009d , insert the phrase \u201cwith fixed barriers\u201d\u009d.
U(105) NFPA 101, 37.3.4.1. After the word \u201coccupancies\u201d\u009d, insert the phrase \u201cand multiple story Class B mercantile occupancies\u201d\u009d. <\/td>\n<\/tr>\n
29<\/td>\nU(106) NFPA 101, 37.4.4.8(1)(b). Delete.
S(78SU107)UNFPA 101, 38.1.2.3 Sand 39.1.2.3S. Add new subsectionSsS 38.1.2.3 Sand 39.1.2.3S to read as follows:
S(79SU108)UNFPA 101, 38.3.4.3(2)S and 39.3.4.3(2)S. Delete existing wording and replace with the following: \u201cIt shall sound a fire alarm signal in a constantly attended location and it shall transmit a fire alarm signal to a listed central station.\u201d\u009d
U(109) NFPA 101, 39.1.2.3. Add new subsection 39.1.2.3 to read as follows:
S(80) NFPA 101, 39.2.2.2.3. Delete
S(81SU110)UNFPA 101, 39.2.4.S2(6)S 7. Add new subsection 39.2.4.S2(6)S 7 to read as follows: <\/td>\n<\/tr>\n
30<\/td>\nU(111) NFPA 101, 39.3.4.3(2). Delete existing wording and replace with the following: \u201cIt shall sound a fire alarm signal in a constantly attended location and it shall transmit a fire alarm signal to a listed central station.\u201d\u009d
S(82SU112)UNFPA 101, 40.3.4.3.1, UandU 42.3.4.3.1 Sand 42.8.3.4.3.1S. Delete the text after the word \u201cmeet\u201d\u009d and replace with \u201cSection 9.6.3 as amended\u201d\u009d.
U(113) NFPA 101, 42.3.4.1.2 and 42.3.4.1.3. After the word \u201coccupancies\u201d\u009d add \u201cless than 3 stories\u201d\u009d.
S(83) NFPA 101, 42.8.2.2.3.1. Add the following: \u201cStairs complying with 7.2.2.5.1 are not required in open parking structures.\u201d\u009d
U(114) NFPA 101, 42.8.2.2.3.2. Add the following: \u201cStairway Identification in accordance with 7.2.2.5.4 shall be provided.\u201d\u009d
S(84) NFPA 101, 42.8.2.2.9. Add the following: \u201cThe two accessible rooms or spaces separated from each other by smoke-resistant construction in accordance with the definition of \u2018area of refuge\u2019 in 3.3.18 shall not be required in open parking structu…
S(85) NFPA 101, 42.8.2.6. Add the following: \u201cIn open parking structures travel distance is permitted to be measured to the closest riser of an open stair providing means of egress to the exterior of the building.\u201d\u009d
U(115) NFPA 101, 42.8.3.4.3.1. Delete the text after the word \u201cshall\u201d\u009d and replace with \u201cmeet Section 9.6.3 as amended\u201d\u009d. <\/td>\n<\/tr>\n<\/table>\n","protected":false},"excerpt":{"rendered":"

Ordinance No. O-21-10 – Adopted Fire Safety Code Amendments<\/b><\/p>\n\n\n\n\n
Published By<\/td>\nPublication Date<\/td>\nNumber of Pages<\/td>\n<\/tr>\n
MD<\/b><\/a><\/td>\nN\/A<\/td>\n42<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n","protected":false},"featured_media":78316,"template":"","meta":{"rank_math_lock_modified_date":false,"ep_exclude_from_search":false},"product_cat":[2722],"product_tag":[],"class_list":{"0":"post-78315","1":"product","2":"type-product","3":"status-publish","4":"has-post-thumbnail","6":"product_cat-md","8":"first","9":"instock","10":"sold-individually","11":"shipping-taxable","12":"purchasable","13":"product-type-simple"},"_links":{"self":[{"href":"https:\/\/pdfstandards.shop\/wp-json\/wp\/v2\/product\/78315","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/pdfstandards.shop\/wp-json\/wp\/v2\/product"}],"about":[{"href":"https:\/\/pdfstandards.shop\/wp-json\/wp\/v2\/types\/product"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/pdfstandards.shop\/wp-json\/wp\/v2\/media\/78316"}],"wp:attachment":[{"href":"https:\/\/pdfstandards.shop\/wp-json\/wp\/v2\/media?parent=78315"}],"wp:term":[{"taxonomy":"product_cat","embeddable":true,"href":"https:\/\/pdfstandards.shop\/wp-json\/wp\/v2\/product_cat?post=78315"},{"taxonomy":"product_tag","embeddable":true,"href":"https:\/\/pdfstandards.shop\/wp-json\/wp\/v2\/product_tag?post=78315"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}